Omron DR 170 14 Benutzerhandbuch

Seite von 67
Klinkmann Automation Omron Ethernet DAServer 
37 
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3                                                                 17014m13  
C200HX/C200HG/C200HE PLCs 
The following table lists the supported item names for the C200HXC200HG and 
C200HE PLCs. 
  
Memory Area 
Prefix 
Tag 
Type  
Address Range 
Value 
Range  
Suffix 
Internal Relay Area 1, 2 
Special Relay Area 1, 2 
(Bit status) 
 IR 
Discrete   IR0:00...IR511:15 
or 
0.00...511.15 
0, 1 
 
Internal Relay Area 1, 2 
Special Relay Area 1, 2 
(Word contents) 
IR 
Integer 
IR0... IR511 
or 
0…511 
(*) 
u s b f g l 
m d e c 
Link Relay Area  
 (Bit status) 
LR 
Discrete 
LR0:00...LR63:15 
 
0, 1 
 
Link Relay Area  
(Word contents) 
LR 
Integer 
LR0... LR63 
(*) 
 
Holding Relay Area  
 (Bit status) 
HR 
Discrete  HR0:00... HR99:15 
 
0, 1 
 
Holding Relay Area  
(Word contents) 
HR 
Integer 
HR0... HR99 
(*) 
u s b f g l 
m d e c 
Auxiliary Relay Area  
 (Bit status) 
AR 
Discrete  AR0:00... AR27:15 
 
0, 1 
 
Auxiliary Relay Area  
(Word contents) 
AR 
Integer 
AR0... AR27 
(*) 
u s b f g l 
m d e c 
Timer/Counter Area 
Completion Flag(****) 
TC 
Discrete 
TC0... TC511 
0, 1 
 
Timer/Counter Area 
(PV) 
PV 
Integer 
PV0... PV511 
(*) 
u s b f g l 
m d e c 
Data Memory Area  
(Bit status)(**) 
DM 
Discrete 
DM0:00... 
DM9999:15 
0, 1 
 
Data Memory Area  
(Word contents)(**) 
DM 
Integer 
DM0... 
DM9999 
(*) 
u s b f g l 
m d e c 
Extended Data Memory 
Area (Bit status)(***) 
EM 
Discrete 
EM0:00... 
EM6143:15 
0, 1 
 
Extended Data Memory 
Area Word contents(***)  
EM 
Integer 
EM0... EM6143 
(*) 
u s b f g l 
m d e c 
 
Item/point names, corresponding to Internal Relay/Special Relay Area may be without 
prefix.  
 
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with 
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is 
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999.  Default 
value range for Integer Tag Type is unsigned integer. 
(**) Memory area range DM7000…DM9999 is supported only if Expansion DM Area is 
allocated on the PLC. 
(***) Current bank only (Memory Area code 98).