Omron CS1W-RPT01 Benutzerhandbuch

Seite von 401
283
Troubleshooting Using Indicators
Section 9-1
Configuring a Network with 32 Nodes or Less
9-1-2
C200HX/HG/HE and CQM1H-series Controller Link Units
Troubleshooting with RUN, ERC, ERH and INS Indicators
The RUN, ERC, ERH, and INS indicators can be used to check whether Con-
troller Link Unit startup and Network participation are operating normally.
Note Be sure to turn off the power to the PLC before performing any of the follow-
ing.
• Disconnecting the Unit or connectors.
• Securing Units or connectors.
• Setting hardware switches.
Problem
Status
Cause and Remedy
The node is not 
present in the net-
work. 
(ERC indicator: ON
RUN indicator: OFF
INS indicator: OFF)
The node with the 
ERC indicator ON is 
set to a node 
address of 33 or 
higher.
Reset the node address between 1 and 
32, then turn the power OFF and ON 
again.
The maximum num-
ber of nodes in the 
network is set to 62.
A CS1W-CLK21-V1 
or CJ1W-CLK21-V1 
is present in the net-
work.
The Wired Network 62 Node Enable Bit 
in the DM Parameters Area of the 
CS1W-CLK21-V1 or CJ1W-CLK-V1 is 
ON. Turn OFF the Wired Network 62 
Node Enable Bit, then turn the power 
supply OFF and ON again.
The data link status 
is showing statuses 
for 62 nodes.
The corresponding 
node is a CS1W-
CLK21-V1 or CJ1W-
CLK21-V1.
The network partici-
pation status is 
showing statuses for 
62 nodes.
RUN: Operating
ERC: Communications 
error
INS: Network 
participation
LNK: Data 
link
M/A: Data 
link 
mode
TER: 
Terminating resistance set
RUN
ERC
INS
SD
RD
M/A
LNK
TER
ERH
  CLK21
CQM1H-series Unit
C200HX/HG/HE Unit
RUN
ERC
INS
SD
RD
M/A
LNK
TER
ERH
  CLK21
Indicators
Probable cause
Probable remedy
RUN
ERC
ERH
INS
Lit
Not lit Not lit Lit
Unit operating normally; 
Network participation nor-
mal.
---
Not lit Lit
---
---
Controller Link Unit faulty.
If the ERC indicators still 
lights when the Unit is 
mounted on another PLC, 
replace the Controller Link 
Unit.