Troubleshooting Using Indicators
Section 9-1
Not lit Not lit Not lit Not lit Power is not being sup-
plied correctly to the PLC.
Check the power supply 
voltage and supply at the 
recommended voltage.
The Controller Link Unit 
has become loose.
Secure the Controller Link 
Unit firmly.
The Bus Connection Unit 
has become loose.
Tighten the mounting 
screws on the Bus Con-
nection Unit.
The Controller Link Unit is 
mounted in the wrong slot.
Refer to  C200HX/HG/HE 
PLCs 
an CJ-series PLCs 
and mount the Unit cor-
rectly.
The Controller Link Unit is 
faulty.
If the indicators do not light 
when the Unit is mounted 
on another PLC, replace 
the Controller Link Unit.
Lit
Lit
---
Not lit The node address is out-
side the setting range.
Reset the node address to 
within the 1 to 32 range.
The same node address is 
being used by two different 
Units.
Reset so that each node 
address is used only once 
within the same Network.
Lit
---
Lit
---
Routing table setting error 
or a Routing Table Enable 
Bit setting error.
Remake and set the rout-
ing table correctly, referring 
to 7-4 Setting Routing 
Tables
. When no routing 
table is being used, turn 
OFF the Routing Table 
Enable Bit.
The Unit is mounted to a 
non-compatible PLC.
Refer to 1-2-4 Controller 
Link Unit Models and PLCs
 
and reinstall the Unit on 
the appropriate PLC.
An error has occurred in 
the PLC.
Refer to the PLC’s opera-
tion manual and correct 
the error. If the error occurs 
again, replace the PLC.
EEPROM error
Refer to 9-2 Status Area 
and Troubleshooting
, cor-
rect the data where the 
error has occurred, and 
reset the Unit. If the error 
occurs again, replace the 
Controller Link Unit. 
Indicators
Probable cause
Probable remedy
RUN
ERC
ERH
INS