Installing and Removing a Power Supply
Matrix X16-C Chassis Installation Guide 3-13
Attaching the Electrostatic Discharge Wrist Strap
The Electrostatic Discharge (ESD) wrist strap must be attached before handling the power
supplies, fan tray, and modules used in the Matrix X16‐C chassis.
supplies, fan tray, and modules used in the Matrix X16‐C chassis.
Place the ESD wrist strap on your wrist and plug the other end into the grounding receptacle,
shown in
shown in
, near the bottom of the chassis.
Figure 3-10 ESD Grounding Receptacle
Installing and Removing a Power Supply
Matrix X AC power supplies are supported in all Matrix X chassis models and provide two power
output levels relative to the input power source. The power supplies support either 110 Vac 20A or
220 Vac 10A service, providing 1160 or 1500 Watts per power supply depending upon the
electrical infrastructure of the site where the Matrix X chassis will be located.
output levels relative to the input power source. The power supplies support either 110 Vac 20A or
220 Vac 10A service, providing 1160 or 1500 Watts per power supply depending upon the
electrical infrastructure of the site where the Matrix X chassis will be located.
Because system components consume varying amounts of electrical power, we recommend
consulting the module power specifications in “
consulting the module power specifications in “
” on page A‐2 to guide you in installing the proper number of power supplies
for your configuration.
As you add modules to the Matrix X16‐C chassis, you may be required to install more power
supplies. Additional power supplies can be installed to provide redundancy. This would require
incremental power be added to the base power requirements of the chassis and its components,
depending on the power redundancy you want to support.
supplies. Additional power supplies can be installed to provide redundancy. This would require
incremental power be added to the base power requirements of the chassis and its components,
depending on the power redundancy you want to support.
When at least two power supplies are installed, the power from each is evenly distributed. If one
power supply fails, the second power supply assumes the load. Additional modules share the
load as required.
power supply fails, the second power supply assumes the load. Additional modules share the
load as required.
Be aware that when you receive your Matrix X16‐C chassis, a coverplate will be in place over all
power supply slots except PS1 in the lower right. This slot is left open for your convenience when
installing the first power supply.
power supply slots except PS1 in the lower right. This slot is left open for your convenience when
installing the first power supply.
1 Grounding Receptacle
2 Plug
3 Wrist strap