Configuration saving and switching
Saving the configuration
When a parameter is modified via the drive’s integrated display terminal or graphic display terminal, this parameter is automatically saved
to the EEPROM non-volatile memory.
to the EEPROM non-volatile memory.
When a parameter is modified using a PLC or an HMI terminal via a network (Modbus, CANopen or a network card), this parameter is written
to the current configuration in the RAM volatile memory. It is not saved to the EEPROM non-volatile memory. If the drive control voltage is
disconnected, when it is reconnected, the parameter reverts to the initial value and the setting is lost.
to the current configuration in the RAM volatile memory. It is not saved to the EEPROM non-volatile memory. If the drive control voltage is
disconnected, when it is reconnected, the parameter reverts to the initial value and the setting is lost.
Display
terminal
Current
configuration
(RAM)
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Display
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Current
configuration
(RAM)
No
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network