Configuration saving and switching
 
Saving the configuration
When a parameter is modified via the drive’s integrated display terminal or graphic display terminal, this parameter is automatically saved 
to the EEPROM non-volatile memory.
When a parameter is modified using a PLC or an HMI terminal via a network (Modbus, CANopen or a network card), this parameter is written 
to the current configuration in the RAM volatile memory. It is not saved to the EEPROM non-volatile memory. If the drive control voltage is 
disconnected, when it is reconnected, the parameter reverts to the initial value and the setting is lost.
Display 
terminal
Current 
configuration
(RAM)
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Display 
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Current 
configuration
(RAM)
No
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network