Commissioning (software) 
 
4.6 Using drive-related I/Os by SIMOTION 
D410 
Commissioning Manual, 08/2008 Edition 
103
 
Configuring of local measuring inputs on the D410 
Local measuring inputs are always permanently assigned to an axis (drive). They are 
configured separately for each drive. The drive and the probe input must always be located 
on the same control unit. The measuring results are transferred using the axis message 
frame in accordance with the PROFIdrive profile. Message frame 39x does not need to be 
configured for local measuring inputs.  
The settings for the use of the local measuring inputs must be made in the expert list. 
Table 4-7 
Local measuring inputs, required settings in the expert list 
 
Parameters in the expert list of the CU 
Parameterization as
p728[8] (DI/DO 8) 
Input 
p728[9] (DI/DO 9) 
Input 
p728[10] (DI/DO 10) 
Input 
DI/DO parameterization as input 
on the control unit 
p728[11] (DI/DO 11) 
Input 
 
Parameters in the expert list of the drive 
Parameterization as
p488[0]  
(measuring input 1 input terminal, encoder 1) 
p488[1]  
(measuring input 1 input terminal, encoder 2) 
p488[2]  
(measuring input 1 input terminal, encoder 3) 
p489[0]  
(measuring input 2 input terminal, encoder 1) 
p489[1]  
(measuring input 2 input terminal, encoder 2) 
Specification of the input 
terminal of the measuring input 
in the expert list of the drive 
p489[2]  
(measuring input 2 input terminal, encoder 3) 
DI/DO 9, 
DI/DO 10 or 
DI/DO 11 
Because a maximum of three encoders can be assigned to a drive, the index [1..2] specifies 
whether the measurement applies to 1, 2 or 3. 
The following must be taken into account: 
●  Only two Measuring Input TOs can be configured per Axis TO or External Encoder TO. 
●  Only one Measuring Input TO can be active on an Axis TO or External Encoder TO. 
Table 4-8 
Local measuring inputs, configuration of the Measuring Input TO 
Axis measuring system no.  Under axis measuring system number, enter the number of the used 
encoder system (namely, encoder 1, 2 or 3). Encoder system 1 is the 
default setting. 
Local measuring 
Activate the checkbox when a local measuring input is used. 
Measuring input number 
Enter here which measuring input is used (namely, 1 or 2). Input 1 is 
the default setting. 
Detailed information is contained in the 
SIMOTION Motion Control Output Cams and 
Measuring Outputs
 Function Manual.