Configuring SIMOTION D410 
 
3.4 Configuring PROFINET (only for D410 PN) 
D410 
Commissioning Manual, 08/2008 Edition 
59
 
Rules for SIMOTION D410 PN 
The general rule for SIMOTION D410 specifies that the send cycle (D410 PN) forms the 
basic clock of the cycle system. All cycles longer than this basic clock must be an integer 
multiple of the basic clock.  
This rule also applies to SINAMICS cycles, if one of the successive cycles is longer than the 
basic clock: 
●  Speed controller p115[1] 
●  Flow controller p115[2] 
●  Setpoint channel p115[3] 
●  Position controller p115[4] 
●  Positioning p115[5] 
●  Technology controller (p0115[6]) 
●  Onboard I/O p0799 
●  Terminal module I/O p4099 
The corresponding cycle must be an integer multiple of the basic clock. 
If any change to the send cycle violates this rule you must also change the SINAMICS 
cycles. In order to change the cycles in the Expert list of SIMOTION SCOUT, select the 
"Control_Unit" from "SINAMICS_Integrated" in the Project Navigator, and then open the 
"Expert List" by selecting the "Expert" command from the shortcut menu. 
Example: A default value of 4 ms is set at the SINAMICS setpoint channel. If setting a DP 
cycle of 3 ms you must set an integer multiple value as required at the setpoint channel, for 
example, 3 ms or 6 ms. 
 
 
Note 
An overview of errors reported in SINAMICS Integrated is provided in the SINAMICS S 
Parameter Manual