Commissioning (software) 
 
4.3 Configuring the system in online mode 
 
D410 
78
 
Commissioning Manual, 08/2008 Edition 
Procedure 
Now go ahead and adapt your components to suit the application. 
Run the wizards for all DRIVE-CLiQ components to be customized and configure the motor, 
encoder, and process data message frames (PROFIBUS message frame type). 
This procedure corresponds with the description in chapter "Configuring the system in offline 
mode". 
 
 
Note 
If only the message frame type needs to be selected for the edit, you can also set this in the 
"Configuration" screen form of the drive element. A HW Config match is then required. 
 
4.3.5 
Aligning HW Config 
See also 
4.3.6 
Download the project to SIMOTION D410 
After having aligned HW Config, download the configuration to SINAMICS Integrated. 
1.  Save and compile the project. 
2.  Go online to SIMOTION D410. 
3.  Select the "Download project to target system" command to download the project to 
SIMOTION D410. The connection to SINAMICS Integrated is activated automatically. 
Drive programming and commissioning is completed. You can now test the drive using the 
drive control panel.