Commissioning (software) 
 
4.3 Configuring the system in online mode 
 
D410 
76
 
Commissioning Manual, 08/2008 Edition 
3.  Select either a servo or a vector drive object. 
4.  Click "Close" to complete automatic configuration. 
The configuration data is uploaded (Upload to PG) automatically as soon as automatic 
commissioning is completed. 
 
 
 
Note 
If the firmware of the SINAMICS components differs from the firmware on the CF card, 
the firmware of the SINAMICS components will be upgraded automatically.  
5.  Click "Close" to exit automatic configuration. 
 
Figure 4-14  Automatic configuration completed 
6.  Perform the "Copy RAM to ROM ..." function on the D410 and on SINAMICS Integrated. 
This saves the project on the CF card and does not need to be reloaded after a switch-
on/switch-off. 
 
 
 
Note 
After having updated the firmware of a SINAMICS component, go offline and then switch 
off the power supply of the upgraded component (Power Off/On). 
Result 
The DRIVE-CLiQ components transferred to the user project by means of the automatic 
configuration are displayed in the Project Navigator.