A uniform temperature must be maintained in the 
motor to obtain constant resistance readings.  When 
the megger readings remain constant, the drying 
process is complete and may be discontinued. 
 
Check for other causes if readings are still low. 
 
Warm Air Oven Drying 
1.  Remove bearing housings. 
2.  Remove rotor. 
 
Bake in oven at temperatures specified in Insulation 
Drying Temperature table, and follow procedures 
described for drying insulation. 
 
Electric Strip Heater Drying 
1.  Remove bearing housings. 
2.  Remove rotor. 
3.  Direct a fan on stator to carry away the moisture. 
4.  Attach temperature indicators to winding and 
apply heat as specified in the Insulation Drying 
Temperature table and follow procedures 
described for drying insulation. 
5.  Radiant type heaters are not recommended 
because some parts may become scorched 
before remote parts reach desired temperature. 
 
Circulating Current Drying 
1.  Remove bearing housings. 
2.  Center the rotor in the stator core. 
3.  Wedge fiber strips into the lower part of the air 
gap so rotor does not touch stator core, or 
remove rotor. 
4.  Direct fan on unit to blow away excessive 
moisture. 
5.  Attach temperature indicators to windings. Do not 
exceed the drying temperatures in the Insulation 
Drying Temperature table. 
6.  An external source of current can be used to 
circulate direct current through the winding of any 
type of alternating current motor. A portable low 
voltage motor-generator set, such as is used for 
welding, is usually suitable. 
 
CAUTION
 
High temperatures. 
May cause damage to insulation. 
Avoid hot spots and radiant type heat 
 
 
When this method is used on the stator, the stator 
phases may be connected in series or in parallel to 
suit the available power supply if both ends of all 
phases are accessible.  If only three leads are 
brought out of the motor, the current may be 
circulated between one terminal and the other two 
connected together.  If this is done, the temperature 
of the single lead connection must be checked 
frequently, and it is desirable to shift the leads 
occasionally.  Usually 50 to 100% of full load current 
will produce the required temperature. The dc voltage 
required for this current will be 0.25  -  5.0% of the 
normal voltage per phase, and the corresponding 
power will be 0.50 - 3.25% of the rating. 
 
Alternating current can be used on the stators of 
squirrel cage induction motors if the rotors are 
removed.  Alternating current is usually not as easy 
to control as required voltage control, and a.c. 
requires a higher voltage source, approximately 10 to 
30% of the rated winding voltage.  In addition, care 
must be taken that miscellaneous parts adjacent to 
the windings, such as lead studs, core supporting 
member, etc., do no overheat due to induced 
currents and the lack of normal ventilation. 
 
CAUTION
 
High temperatures. 
May cause damage to insulation. 
Avoid hot spots and radiant type heat 
 
Bearings 
Long life of bearings is assured only by maintaining 
proper alignment and good lubrication at  all  times.  
Some factors that can cause excessive bearing noise 
and heat are: 
 
1.  Incorrect alignment of couplings. 
2.  Excessive or wrong direction of thrust. 
3.  Improper lubrication. 
 
Bearing Lubricants - Grease 
Prior to shipment, bearings are lubricated with the 
proper amount and grade of grease to provide 
satisfactory service under normal operation and 
conditions.  See the lubrication plate mounted on the 
motor for regreasing intervals and recommended 
type of grease.  It is good practice, however, to check 
bearings of newly installed machines for proper 
lubrication.