Mitsubishi Electronics QD75MH2 Benutzerhandbuch

Seite von 838
 
 
 
10 - 25 
MELSEC-Q
 
10   HIGH-LEVEL POSITIONING CONTROL 
 
 Start time chart  
 
The following chart shows a time chart in which the positioning data No. 1, 2, 10, 
11, and 12 of axis 1 are continuously executed as an example.  
 
(1)   Block start data setting example 
 
Axis 1 block 
start data 
 Da.11   
Shape 
 Da.12   
Start data No. 
 Da.13   
Special start 
instruction 
 Da.14   
Parameter 
1st point 
1: Continue 
0: Block start 
– 
2nd point 
0: End 
10 
0: Block start 
– 
 
 
 
 
 
 
 
 
 
 
 
(2)   Positioning data setting example 
 
Axis 1 position-
ing data No. 
 Da.1  
Operation pattern 
11: Continuous path control 
00: Positioning complete 
 
 
10 
11: Continuous path control 
11 
11: Continuous path control 
12 
00: Positioning complete 
 
 
 
(3)   Start time chart  
 
[Y10]
PLC READY signal
QD75 READY signal
[X10]
[XC] 
Positioning complete signal 
V
t
Error detection signal
Positioning data No. 
Dwell time 
12(00)
Operation pattern 
1(11)
1st point [buffer memory address 26000]
2nd point [buffer memory address 26001]
11(11)
10(11)
2(00)
7000
1
-32767
10
(8001
H
)
(000A
H
)
Cd.3  Positioning start No.
Cd.4  Positioning start point No.
Positioning start signal
[X0]
Start complete signal
BUSY signal
[X8]
[X14]
[Y0]
All axis servo ON
[Y1]
Dwell time 
 
Fig. 10.3 Start time chart for high-level positioning control (block start)