Mitsubishi Electronics QD75MH2 Benutzerhandbuch

Seite von 838
 
 
 
14 - 9 
MELSEC-Q
 
14   DEDICATED INSTRUCTIONS 
 
END 
processing
END 
processing
END 
processing
END 
processing
OFF
OFF
OFF
ON
ON
ON
When 
completed 
abnormally
When 
completed normally
1 scan
TEACH    instruction
execution completion
PLC program
TEACH    instruction
Complete device
Complete state display 
device
 
 
[Errors] 
(1)  When a TEACH instruction is completed abnormally, the error complete signal 
((D)+1) is turned ON, and the error code is stored in the complete status (S)+1. 
Check and take a measure against the error referring to section 15.2 "List of error 
codes". 
 
[Precautions] 
(1)  The following dedicated instructions cannot be executed simultaneously for the 
same axis. 
(Can be executed simultaneously for different axes.) 
  • Positioning start instructions  (PSTRT1 to PSTRT4) 
  • Teaching instructions (TEACH1 to TEACH4) 
 
(2) The TEACH  instruction can only be executed when the BUSY signal (XC, XD, 
XE, XF) is turned OFF. 
When the BUSY signal is turned ON, the TEACH  instruction will not be 
executed. (not processed.) 
Before executing the PFWRT instruction, make sure that the BUSY signal for the 
axis to be processed is turned OFF. 
 
(3)  When the remote I/O station* (Q Corresponding MELSECNET/H network remote 
I/O module) is used, the dedicated instruction (TEACH ) is unusable. 
 
: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H 
Network System Reference Manual (Remote I/O Network). 
 
(4)  If the TEACH  instruction is executed in any of the following cases, an error 
"Dedicated instruction error" (error code: 804) will occur and teaching cannot be 
performed. 
  • Any value other than 0 and 1 is set to "Teaching selection" (device: (S)+2) of 
the control data. 
  • Any value other than 1 to 600 is set to "Positioning No." (device: (S)+3) of the 
control data.  
  • The instruction for a non-existent axis is specified.  
(Example: The TEACH2 instruction is specified when the QD75MH1 is used.)