3 DESCRIPTION 
 
3.1 
BLOCK DIAGRAM AND MAIN ELEMENTS 
Fig. 3.1-1   Block diagram 
 
The 
SG Series system can be divided into the following main elements: 
 
Control System 
SG Series  is designed with microprocessor-controlled signal 
processing circuits. The interface between the operator and the unit is provided by the 
monitoring system on the front panel. 
This monitoring system consists of an active mimic diagram, a keyboard and a backlit 
display. 
 
Rectifier 
The standard Rectifier consists of a 6-pulse SCR-bridge, which 
converts the 3-phase Utility Voltage into a controlled and regulated DC-voltage. 
This regulated DC-voltage is used to supply power to the Inverter, and to provide charging 
power to the Battery
 
Inverter 
The  Inverter converts the DC voltage into a three-phase AC-
voltage with constant amplitude and frequency, which is completely independent and isolated 
from the AC-input voltage. 
 
Automatic Bypass 
The Automatic Bypass consists of a static semiconductor-switch 
(SSM: Static Switch Module), used to provide an uninterrupted transfer of the Load from 
Inverter to Utility. 
 
Back-feed Protection 
All 
SG Series UPS's are equipped with an automatic system for 
the protection against voltage back feeding towards Utility, through the Bypass (Applied 
Standard IEC 62040-1). 
This protection works automatically by opening contactor  K6 and K8 (in series with the 
thyristors of the static switch) and eventually K7, and acts in case of internal defects of the 
system, or due to wrong manipulations on the Manual Bypass Q2
 
Manual Bypass 
The Manual Bypass consists of a pair of manual switches (Q1 
and  Q2),  which removes the UPS from the Load for maintenance, while still supplying the 
Load
 with power directly from the Utility. 
 
Battery 
The  Battery  supplies the DC power to the Inverter when the 
Utility is out of accepted tolerances.