9-4 RS-485 Modbus RTU Serial Communications 
The serial interface supports operation, configuration and monitoring of inverter functions through an 
EIA/RS-485 connection. The serial interface is based on Modbus RTU protocol. This protocol allows the 
inverter to function as an RTU slave on an industrial network. 
 
9-4-1 Transmission Specification 
Item Specification 
Physical level 
EIA/RS-485 
Transmission distance 
1600 ft (500 m) 
Number of nodes 
32 total 
Transmission speed 
19200, 9600, 4800, 2400 [bits/s] 
Transmission mode 
Half duplex 
Transmission protocol 
Modbus RTU 
Character code 
Binary 
Character length 
8 bits 
Error check 
CRC 
 
9-4-2 Connection 
Connection method 
Use shielded wire and connect to the control terminals (DX-, DX+ and SD). A termination resistor should be 
added between the data lines on the each end of the network. The value of the termination resistor 
depends on the characteristic impedance of the cable. A common value for termination resistors is 120 
ohms. 
 
Control terminals 
Terminal 
marking 
Terminal name 
Function description 
DX+ 
RS-485 communication data (+) 
DX- 
RS-485 communication data (–) 
Input/output terminals for RS-485 
communication. 
SD 
Cable shield 
Electrically floating 
 
9-4-3 Serial Interface Configuration 
Inverter function codes H30 to H39 are used to configure the serial interface parameters, such as device 
address, baud rate and error response. 
 
9-4-4 Modbus RTU Functions 
The following RTU functions are supported. The maximum number of consecutive parameters for function 
03 and 16 messages is 16. 
 
Code Description 
03 
Read Holding Registers (16 registers maximum) 
06 Preset 
Single 
Register 
16 
Preset Multiple Registers (16 registers maximum)