Panamax MB1000 Benutzerhandbuch

Seite von 45
12
RS-232 Communications Protocol & Command Set
BATTERY LEVEL STATUS
Requests the battery level, expressed as a percentage of maxi-
mum (full charge).
Send Query to UPS: 
?BATTERYSTAT<CR>
Action:   
 
Load level will be displayed
Response: 
 
$BATTERY = xxx<CR>
xxx is the battery charge level (percentage of maximum charge) 
expressed in decimal format.  If the value is less than 100, the 
hundreds digit is represented with a 0.
____________________________________________
LIST CONFIGURATION
Requests a list of all configurable parameters and current settings.
Send Query to UPS: 
?LIST_CONFIG<CR>
Action:   
 
List of configurable parameters and  
 
 
 
current settings will be displayed.
Response: 
 
$BTHRESH = level<CR>
 
 
 
$BUZZER = mode<CR>
 
 
 
$AVR = mode<CR>
 
 
 
$FEEDBACK = mode<CR>
 
 
 
LINEFEED = mode<CR>
 
 
 
$BRIGHTNESS = xxx<CR>
 
 
 
$SCROLL_MODE = xxx<CR>
 
 
 
$SLEEP_MODE = xxx<CR>
____________________________________________
List of all commands and queries
Send Query to UPS: 
?HELP<CR>
Action:   
 
List of all commands and queries  
 
 
 
will be displayed
Response: 
 
!ALL_ON<CR>
 
 
 
!ALL_OFF<CR>
 
 
 
!SWITCH<CR>
 
 
 
!SET_BATTHRESH<CR>
 
 
 
!SET_BUZZER<CR>
 
 
 
!SET_AVR<CR>
 
 
 
!SET_FEEDBACK<CR>
 
 
 
!SET_LINEFEED<CR>
 
 
 
!RESET_ALL<CR>
 
 
 
 
!SET_BRIGHT<CR>  
    ?VOLTAGE<CR>
 
!SET_SCROLLMODE<CR>      ?LOADSTAT<CR>
 
!SET_SLEEPMODE<CR>       ?BATTERYSTAT<CR>
 
?ID<CR>  
 
   ?LIST_CONFIG<CR>
 
?OUTLETSTAT<CR> 
    ?HELP<CR>
 
?POWERSTAT<CR> 
    
_________________________________________
RESPONSES & MESSAGES
OUTLET STATUS CHANGE
CONDITION 
 
RESPONSE
Outlet Bank 1 changes state  $BANK1 = status<CR>
Outlet Bank 2 changes state  $BANK2 = status<CR>
status = {ON, OFF}
_________________________________________
POWER BUTTON STATUS CHANGE
CONDITION 
 
RESPONSE
Power Button changes  
$BUTTON = status<CR>
ON/OFF status 
 
status = {ON, OFF}
_________________________________________
POWER FAULT STATUS CHANGE
CONDITION 
 
RESPONSE
Overvoltage State   
$PWR = OVERVOLTAGE<CR>
Undervoltage State 
$PWR = UNDERVOLTAGE<CR>
Lost Power State   
$PWR = LOST POWER<CR>
Test Mode 
 
$PWR = TEST<CR>
Recovery Mode   
$PWR = RECOVERY<CR>
Normal Operation Mode  $PWR = NORMAL<CR> 
 
Low Battery 
 
$LOWBAT<CR>
AVR Stage 
 
$AVRSTATE = state<CR>
 
 
 
state = {BOOST, BUCK}
Remaining Backup Time  $TIME = xxx<CR>
 
 
 
xxx = backup time
Battery State 
 
$BATTSTATE = xxx<CR>
 
 
 
xxx = {CHARGE, DISCHARGE, FULL}
Power Control Software