Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
6.2
To install a Supervisory Contact Module:
1.
Securely mount the SCM.
2.
Install wiring from the SCM using ½-in. conduit through the cable entry panels
in the top of the SSBM control section (refer to the enclosed switchboard
vendor drawings for the location of the conduit landing plate).
3.
If not already installed, locate the RMP adapter cable assembly (see
Figure 6---2) in the spare parts kit. Mate the DB---9 connector on the back of
the terminal block to the DB---9 connector (Port 1) on the Customer Interface
Panel of the SSBM (refer to Drawing 164201373---4 in Appendix A). Use two
screws from the spare parts kit to secure the terminal block bracket to the
Customer Interface Panel.
TERMINAL
BLOCK
FUSE
(TB3)
Connect to
Port 1 (DB---9) on
Customer Interface Panel
Figure 6---2. Terminal Block Bracket