Technicolor - Thomson TS 870 Benutzerhandbuch

Seite von 46
APPENDIX “B” 
 
THOMSON TECHNOLOGY
©
 
 
 
INSTRUCTIONS TO CHANGE SYSTEM 
VOLTAGE ON TS 870 SERIES TRANSFER 
SWITCHES WITH TSC 80 CONTROLLER 
 
 
9087A - 198
th
 Street, Langley, B.C. Canada V1M 3B1 • Telephone (604) 888-0110 • Telefax (604) 888-3370
 
DANGER!!!! 
Arc Flash and Shock Hazard. Will cause severe injury or death. 
 
Do not open equipment until ALL power sources are disconnected 
 
This equipment must be installed and serviced only by qualified electrical personnel 
utilizing safe work practices and appropriate Personal Protective Equipment (PPE). 
Failure to do so may cause personal injury or death 
 
 
1. 
Ensure all power sources are de-energized prior to opening the transfer switch enclosure door.
 
2. 
Disconnect “Control Circuit Isolation Plug”
 
3. 
Change voltage transformer primary taps settings to match new system voltage on all potential 
transformers. (Refer to wiring schematic diagram Figure 1). Ensure all electrical connections are 
tight.
 
4. 
Remove rear cover on door mounted TSC 80 transfer controller. 
5. 
Change voltage jumper setting to desired system voltage (Refer to Figure 2).  
Note: 208V systems do not require a jumper on any pins. 
6. 
Re-install rear cover for TSC 80 transfer controller. 
7. 
Record new programmed voltage on calibration label on TSC 80 rear cover 
8. 
Re-connect “Control Circuit Isolation Plug”.
 
9. 
Remove all tools and close transfer switch enclosure door.