FieldServer FS-RA-CLX-BAS Benutzerhandbuch
FS-RA-CLX_SlotServer_Instruction_Manual_(T17011)
Page 15 of 34
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com
7.
Programming the ControlLogix CPU for a small SlotServer Interface
The discussion that follows describes the basic steps to set up and test the system for
transferring data between CPU tags and the SlotServer using the I/O image method. The quick
Start example uses LonWorks as the example 3
transferring data between CPU tags and the SlotServer using the I/O image method. The quick
Start example uses LonWorks as the example 3
rd
Party Protocol. A hardcoded template is filled
with Lon variables is created. Each item uses a different amount of bytes and the total adds up
to 104 Lon Network Variables. This limit of 104 does not apply when using customized data
items – the actual limit is 496 bytes. Refer to the Advanced Project to access more than 104
Network Variables.
to 104 Lon Network Variables. This limit of 104 does not apply when using customized data
items – the actual limit is 496 bytes. Refer to the Advanced Project to access more than 104
Network Variables.
7.1.
Step 1: Establish an RSLogix project
5
• Use File/New to create a new project or File/Open to open an existing project.
5
Your Controller may be of a different type to the one shown in the example.
Ensure that this is the slot
number in the rack where
your Controller resides.
number in the rack where
your Controller resides.