7. 
Programming the ControlLogix CPU for a small SlotServer Interface 
The  discussion  that  follows  describes  the  basic  steps  to  set  up  and  test  the  system  for 
transferring data between CPU tags and the SlotServer using the I/O image method.  The quick 
Start example uses LonWorks as the example 3
rd
 Party Protocol.  A hardcoded template is filled 
with Lon variables is created.  Each item uses a different amount of bytes and the total adds up 
to  104  Lon  Network  Variables.    This  limit  of  104  does  not  apply  when  using  customized  data 
items – the actual limit is 496 bytes.  Refer to  the Advanced Project to access more than 104 
Network Variables.  
7.1. 
Step 1: Establish an RSLogix project
5
 
•  Use File/New to create a new project or File/Open to open an existing project. 
 
 
 
                                                 
5
 Your Controller may be of a different type to the one shown in the example. 
Ensure  that  this  is  the  slot 
number  in  the  rack  where 
your Controller resides.