Chapter 7 Remote Drop I/O Data
Forcing an Analog Circuit
If the circuit to be forced is an analog circuit, its current value appears on line 3 of the
Monitor screen.
MNTR           3
143#0.3 %AI    1
STS –22138
> ref force diag
 
a
Circuit  value
Pressing F3 (force) displays:
MNTR           3
143#0.3 %AI    1
FRC –22138
  
 
a
Circuit is
not forced
> ref force diag
Press F2 (force) to enter a forced value for the circuit.  The screen displays:
FORCE TO: ______
   chng entr
Press F2 (chng).  Enter the value, then press F3 (entr).  The forced value appears on 
line 3.
MNTR           3
143#0.3 %AI    1
STS –10000 FRC
  
 
a
Circuit  is  forced
force  release
To release the force, press F4 (release) from the force/release screen.