Compact Refrigerators and Freezers Service and Installation Manual
For customer service, call (888) 732-2446 Fax (800) 669-0619, www.mccallrefrigeration.com
6
Freezer Models MCCSTF27 & MCCF27 Temperature Control Operation
After the unit is connected to power it will automatically 
begin operating. With the doors closed, the temperature of 
the cabinet should reach 0°F (-18°C) on freezers in about 
one hour. Continuous opening and closing of the doors will 
hamper the unit’s ability to maintain optimum temperature.
The electronic temperature control constantly monitors box 
temperature as well as evaporator coil temperature to maintain 
consistent product temperatures. As an added energy-saving 
feature, the electronic controller will switch the evaporator 
fan motor on and off with the compressor and condenser fan 
motor.
At initial start-up or anytime power is disconnected, then 
reconnected to the unit, the control will delay all operations for 
a short time (up to 10 minutes.) While in this delay period, the 
control initializes the control parameters and confirms that the 
temperature sensors and circuits are operational. 
Service Alert: During normal operation the evaporator fan 
may cycle and/or pulse independently of the compressor. 
Consult the service manual or contact Technical Support at 
1-888-732-2446 if you are unsure of the proper function.
IMPORTANT NOTE REGARDING FREEZERS: 
After initializing, the control will immediately enter a DEFROST 
mode.  The compressor and condenser fan as well as the 
evaporator fan will remain off until initial defrost is complete. 
This initial defrost cycle may take up to 15 minutes to 
complete, at which time the freezing cycle will begin. 
Whenever the freezer is plugged in, and the control has 
completed initializing including the initial defrost cycle (see 
above), the electronic temperature control will cycle the 
compressor, evaporator fan motor, and condenser fan motor 
to maintain box temperature at the control setting.  
Freezer Automatic Defrost
The control also monitors compressor total running time 
and will enter a defrost cycle after total compressor running 
time is greater than 5-hours since the last defrost cycle OR 
if evaporator coil temperature drops below -34°F (indicating 
excessive frost on the coil).
Freezer Manual Defrost
If a manual defrost is desired, simply unplug the unit for 
several seconds, then plug unit back in. This will cause the 
control to re-initialize and then enter a defrost cycle.
When the control enters the defrost mode, whether manual 
or automatic, it switches off the evaporator fan motor, 
compressor and condenser fan motor, and switches on the 
defrost heater to warm the evaporator coil and melt all frost 
accumulated during the previous refrigeration cycle. The 
control will continue the defrost cycle for a MINIMUM of 8 
minutes and a MAXIMUM of 30 minutes depending on the 
amount of frost accumulated on the evaporator coil.
After the defrost cycle is complete, the control returns to a 
normal refrigeration cycle, however the evaporator fan motor 
will not switch on for 2 minutes AFTER the compressor and 
condenser fan motor have begun operating. 
Electronic Temperature Control Location & Adjustment
Never turn the knob more than 1 dial number and always 
allow 8 hours for temperature stabilization before making 
any additional adjustments. The control is located in the 
control box at the rear of the unit (see photo).  It is factory set 
at mid-range to maintain about -3°F (-18°C) box temperature. 
To adjust for colder temperatures, turn the knob clockwise. 
For warmer temperatures, turn the knob counter-clockwise. 
Turn the knob fully counter-clockwise to turn the refrigeration 
system off. 
Freezer Models MCCF48 & MCCSTF48 Temperature Control Operation
After the unit is connected to power it will automatically begin 
operating. With the doors closed, the temperature of the 
cabinet should reach 0°F (-18°C) on freezers in about one 
hour. 
A thermostat located in the evaporator housing on interior rear 
of the unit, controls the temperature in the box. The factory 
setting for the control is “4” and maintains about -3°F (-18°C) 
in the box. Set toward “1” for higher temperatures and toward 
“7” for lower temperatures.
Continuous opening and closing of the doors will hamper the 
unit’s ability to maintain optimum refrigeration temperature.
When the mechanical timer initiates a defrost cycle, power to 
the condensing unit and evaporator fans is interrupted and 
the defrost heater is energized. The defrost heater warms the 
evaporator coil thereby melting all frost accumulated during 
the previous refrigeration cycle. Once all frost is eliminated, 
the temperature of the coil continues to rise until it reaches 27 
minutes. The defrost control switches to refrigeration mode.  
Defrost will initiate every six hours.
Turn the defrost timer screw ONLY in a clockwise 
direction, turning the screw counter-clockwise 
will break the cam motor.
Service Alert
During normal operation the evaporator fan may cycle 
and/or pulse independently of the compressor. Consult 
the service manual or contact Technical Support at 
1-888-733-2446 if you are unsure of the proper function.