Drain Connection (HRV Only)
During a defrost cycle, the HRV may produce some
condensation. This water should flow into a nearby drain, or be
taken away by a condensate pump.
During a defrost cycle, the HRV may produce some
condensation. This water should flow into a nearby drain, or be
taken away by a condensate pump.
The HRV cabinet has prepunched holes for the drain (see
below). Insert the drain spout through the hole in the drain pan.
Do not forget the “O ring” which seals each spout to the pan
REMEMBER TO HAND TIGHTEN ONLY the washer and
lock nut which hold the drain spout in place.
below). Insert the drain spout through the hole in the drain pan.
Do not forget the “O ring” which seals each spout to the pan
REMEMBER TO HAND TIGHTEN ONLY the washer and
lock nut which hold the drain spout in place.
Construct a P-Trap using the plastic tee connector. Cut two
lengths of hose and connect each piece to an end of the “T”
fitting, then connect the other ends to the two drain spouts.
Position the “T” fitting to point upward and connect the drain
line. Tape or fasten base to avoid any kinks. Pour a cup of water
into the drain pan of the HRV after the drain connection is
complete. This creates a water seal which will prevent odors
from being drawn up the hose and into the fresh air supply of
the HRV.
lengths of hose and connect each piece to an end of the “T”
fitting, then connect the other ends to the two drain spouts.
Position the “T” fitting to point upward and connect the drain
line. Tape or fasten base to avoid any kinks. Pour a cup of water
into the drain pan of the HRV after the drain connection is
complete. This creates a water seal which will prevent odors
from being drawn up the hose and into the fresh air supply of
the HRV.
Drain Connections
Note: Secondary drain pan may be required to
protect from condensate leakage.
protect from condensate leakage.
Use drain spout provided in
door. “P” trap must be at least
6” (152 mm) below unit.
door. “P” trap must be at least
6” (152 mm) below unit.
Do not remove
these drain plugs
these drain plugs
1/2” I.D.
condensate line
condensate line
Use “T” between drain pans
to create a “P Trap”. “P” trap
must be at least 6” (152 mm)
below unit.
to create a “P Trap”. “P” trap
must be at least 6” (152 mm)
below unit.
Do not remove
cap from drain spout
cap from drain spout
1/2” I.D.
condensate line
condensate line
Drain trap and tubing MUST be below bottom of
door with 1/4" per foot downwards slope away
from unit.
door with 1/4" per foot downwards slope away
from unit.
CAUTION
The HRV and all condensate lines must be
installed in a space where the temperature is
maintained above the freezing point or freeze
protection must be provided.
installed in a space where the temperature is
maintained above the freezing point or freeze
protection must be provided.
CAUTION
Drain Set-up for Vertical Installation
Drain Set-up for Horizontal Installation
DRAIN
SPOUT
ZIP TIE
TO DRAIN
TEE
CONNECTOR
DRAIN
SPOUT
PRE-PUNCHED HOLES (2)
DRAIN PAN
DRAIN PAN
1/2 " I.D.
DRAIN HOSE
DRAIN HOSE PLUMBING
DRAIN
SPOUT
DRAIN
SPOUT
TO DRAIN
1/2" HARD PIPE
TEE
JOINT
PRE-PUNCHED HOLES (2)
DRAIN PAN
DRAIN PAN
HARD PIPE PLUMBING
"P" Trap (HRV only)
Model RNC120D