DVBR Series Direct Vent Gas Fireplace
20000584
Always check for gas leaks with a mild 
soap and water solution applied with a 
brush no larger than 1” (25 mm). Never 
apply soap and water solution with a spray 
bottle. Do not use an open flame for leak 
testing.
The fireplace valve must not be subjected 
to any test pressures exceeding 1/2 psi. 
Isolate or disconnect this or any other gas 
appliance control from the gas line when 
pressure testing.
The gas control is equipped with a captured screw type 
pressure test point, therefore it is not necessary to pro-
vide a 1/8” test point up stream of the control.
When using copper or flex connector use only approved 
fittings. Always provide a union when using black 
iron pipe so the gas line can be easily disconnected for 
burner or fan servicing. (Fig. 6) See the gas specifica-
tions for pressure details and ratings.
Fig. 9 EB-1 receptacle.
FP580
FP580
INSTA VENT FREE
EB1 JUNCTION BOX
11/18/97
OUTSIDE
ELECTRICAL BOX
�������������
INSIDE
FRONT
 OF UNIT
Remote Switch Installation
Do not wire the remote ON/OFF wall switch 
for this gas appliance into a 120v power 
supply.
1.  Thread wire through the electrical knockout located 
on either side of fireplace. Do not cut wire or insula-
tion on metal edges. Ensure that wire is protected. 
Run the other end to a conveniently located wall 
receptacle box.  
2.  Attach wire to switch and install switch into recepta-
cle box. Attach cover plate to switch.
3.  Connect wiring to gas valve. (Fig. 7)
W584-9
WIRING DIAGRAM
1/8/99   djt
11/9/99 added thermopile
Thermopile
Fig. 7 Remote switch wiring diagram for R models.
W584-9
Switch
Gas Valve
EB-1 Electrical Box
The fireplace, when installed, must be elec-
trically connected and grounded in accor-
dance with local codes or, in the absence 
of local codes, with the current CSA C22.1 
Canadian Electrical Code.
For USA installations, follow the local 
codes and the national Electrical Code 
ANSI/NFPA No. 70.
It is strongly suggested that the wiring of 
the EB-1 Electrical Junction Box be carried 
out by a licensed electrician.
Ensure that the power to the supply line 
has been disconnected before commenc-
ing this procedure.
EB1 (Receptacle) Hook-Up
1.  Remove contents from plastic bag. Remove knock-
out in center of electrical box. Remove coverplate 
from fireplace and knockout. Insert connector 
through coverplate, plate and box. Screw nut on 
connector with screws provided (2) to secure the 
coverplate to the plate.
2.  Connect black positive wire to brass screw (polar-
ized side) of receptacle. The white wire is connected 
to chrome screw. The ground wire is connected to 
green ground screw of the receptacle. Fit receptacle 
into electrical box.
3.  Screw cover plate provided to electrical box.
4.  Secure receptacle to fireplace.
FP297A
INSTA VENT FREE
UVHB26 GAS SUPPLY 
7/1/98
FP297A
Fig.  6   Typical gas supply installation.
1/2” Gas Supply
1/2” NPT X 1/2” Flare Shut-off Valve
3/8” Flex line 
(from valve)