Quattro DC Display Data D0 Menu 
 
 
LS Power Data D3 submenu 
 
Parameter Description 
Units 
Hidden
Item 
LS PWR OUTPUT 
(Line Side Power Output) Estimated power transfer to and from the AC 
Line.  Value is positive when drive is pulling power from the line, and 
negative when drive is delivering power back to the line. 
kW 
DC BUS VOLTAGE 
(DC Bus Voltage) Measured DC Bus voltage as seen by the line side 
controller. 
Volts 
DC BUS VOLTS 
REF 
(DC Bus Voltage Reference) Calculated applied DC Bus Voltage 
reference as the peak of the AC line voltage plus the amount to boost.  
For more information, see Line Side Power Convert A5 Submenu on 
page 46. 
Volts 
LS OVERLOAD 
(Line Side Overload) 
LS INPUT 
CURRENT 
(Line Side Input Current)  Measured input line current as the average 
of the three phases. 
Amps 
LS D AXIS I 
(Line Side D Axis Current)  Percent of rated current in the D axis.  
Note:  This is reactive power producing current. 
LS Q AXIS I 
(Line Side Q Axis Current)  Percent of rated current in the Q axis.  
Note:  This is power producing current. 
LS D AXIS VOLTS 
(Line Side D Axis Voltage)  Percent of rated voltage in the Q axis.  
Note: This is reactive power producing voltage. 
LS Q AXIS VOLTS 
(Line Side Q Axis Voltage)  Percent of rated voltage in the Q axis.  
Note:  This is power-producing voltage. 
INPUT HZ 
(Input Frequency)  Measured input line frequency. 
Hz 
INPUT Vab 
(Input Voltage A-B Phase)  Measured input line-to-line voltage phase 
A-B. 
Volts 
INPUT Vca 
(Input Voltage C-A Phase)  Measured input line-to-line voltage phase 
C-A.   
Volts 
LS MODULE TEMP 
(Line Side Module Temp)  Indicates the hottest of the line side 
converters IGBT modules.   
°C 
Table 1 : LS Power Data D2 Submenu 