Quattro DC Troubleshooting 
 
Name Description 
Possible Causes & Corrective Action 
Cont Pwr Lost 
Motor contactor power was 
removed while the drive was 
commanding it to be 
energized. 
Improper drive On-Run-Stop sequencing 
 
Verify Safety Chain operation  
 
Verify Safety Chain timing 
Contactor Flt 
The command to close the 
contactor and the contactor 
feedback do not match for the 
time specified by the Contact 
Flt Time parameter 
Check parameter settings and contactor 
 
Check CONTACT FLT TIME (A1) parameter 
for the correct contactor fault time.  
 
Verify wiring to logic input 1 (CONTACT 
CFIRM (C2) is correct 
 
Contactor hardware problem 
Cube data Flt 
 
The cube data for the motor 
side processor is invalid. 
Parameters Corrupted 
 
Re-enter parameters and power-cycle 
 
If re-occurs, replace Drive Control board 
Cube ID Fault 
 
The cube identification 
number for the motor side is 
invalid. 
Hardware Problem 
 
Power cycle the drive. 
 
Verify the Cube I.D. is properly connected and 
fully seated 
 
If re-occurs, replace Drive Control board 
Curr Reg Flt 
 
Measured current does not 
match the command current. 
Problem with Motor Contactor 
 
Verify that motor contactor is closing 
 
Verify motor contactor is not opening 
unexpectedly 
Faulty current feedback signals 
 
Verify that reported drive current is zero when 
drive is not operating 
 
Verify connections to current transducers 
Loss of gate power supply 
 
Verify base block jumper is in place 
Incorrect DC Bus Voltage reading 
 
Measure the dc bus with a meter 
 
Compare that with the value on the digital 
operator, DC BUS VOLTAGE (D2) 
Inaccurate Motor Parameters 
 
Verify motor nameplate values (A6) are 
entered correctly 
DCU Data Flt 
 
The DCU parameters 
checksum is invalid on the 
motor side. 
Parameters Corrupted 
 
Check & re-enter parameters and power cycle 
the drive 
 
If re-occurs, replace Drive Control board 
Dir Conflict 
(alarm

 
Declared when the speed 
command is held at zero due 
conflict with the analog speed 
command polarity and the run 
up / run down logic 
DIR CONFIRM (C1) must be 
enabled. 
Check Parameter Settings 
 
 
Sensitivity determined by the ZERO SPEED 
LEVEL (A1) 
Confirm Speed Command Polarity 
 
Check polarity of the analog speed command 
on analog channel #1 
 
Compare that with the RUN UP (positive) and 
RUN DOWN (negative) logic input status 
If nuisance, the function can be disabled by DIR 
CONFIRM (C1) parameter. 
82