Quattro DC Troubleshooting 
 
Name Description 
Possible Causes & Corrective Action 
LS PCU Data 
 
PCU parameters checksum is 
invalid on the line side. 
Parameters Corrupted 
 
Check & re-enter Line Side parameters and 
power cycle the drive 
LS Phase 
 
The line side converter has 
detected the loss of one or 
more phases of the AC line. 
Input Line to Line Phase Loss 
 
Verify all 3 AC line phases are correct 
 
Verify wiring to / from contactor UTM 
 
Verify 3 phase signal wiring to PCB A8 
 
If re-occurs, replace A8 
LS Size 
 
The line side power converter 
has detected that the power 
bridge and current sensors, do 
not match. 
Hardware Mismatch 
 
Size of the power bridge does not match the 
rating as defined on the cube ID board.   
 
Check for correct Cube ID board located on A3 
board 
LS Undr Voltg 
(alarm) 
 
The DC Bus has fallen below 
the under voltage alarm level.  
The alarm level is set by UV 
Alarm Level parameter. 
Low Input Voltage 
 
Check INPUT L-L VOLTS (A5) and UV 
ALARM LEVEL (A4) 
 
Verify proper input voltage and increase, if 
necessary, the input AC voltage within the 
proper range 
 
Check for missing input phase 
 
Check power line disturbances due to starting 
of other equipment 
Drive Accurately Reading the DC Bus 
 
Measure the DC bus with a meter  
 
Compare that with the value on the digital 
operator, BUS VOLTAGE (D2) 
Poor Tuning of Line Side Parameters 
 
Verify Parameters 
Line Converter Problem 
 
Verify the line converter did not shutdown 
while the motor controller was in process of 
regeneration 
LS Undrvolt 
(fault) 
 
The DC Bus has fallen below 
the under voltage fault level.  
The fault level is set by UV 
FAULT Level parameter.  
Low Input Voltage 
 
Check INPUT L-L VOLTS (A5) and UV FAULT 
LEVEL (A4) 
 
Verify proper input voltage and increase, if 
necessary, the input AC voltage within the 
proper range 
 
Check for missing input phase 
 
Check power line disturbances due to starting 
of other equipment 
Drive Accurately Reading the DC Bus 
 
Measure the DC bus with a meter  
 
Compare that with the value on the digital 
operator, BUS VOLTAGE (D2) 
Poor Tuning of Line Side Parameters 
 
Verify Parameters 
Line Converter Problem 
 
Verify the line converter did not shutdown 
while the motor controller was in process of 
regeneration 
89