Magnetek Quattro DC Elevator Drive Benutzerhandbuch

Seite von 126
Quattro DC Troubleshooting 
 
Name Description 
Possible Causes & Corrective Action 
ME Cont Pwr 
 
Motor contactor power was 
removed while the drive was 
commanding it to be 
energized. 
Contactor Problem 
 
Check motor contactor power 
ME Pwr Avail 
 
Motor contactor power was 
not available when the drive 
was commanded to start. 
Contactor Problem 
 
Check motor contactor power 
Module x IGBT 
 
A de-saturation condition has 
been detected on the specified 
motor side IGBT module. 
Incorrect Parameter Settings 
 
Check RATED MOTOR CURR (A6), 
ARMATURE VOLTS (A6), FULL FLD AMPS 
(A6), WEAK FLD AMPS (A6), and FLUX 
CONFIRM LEVEL 
Motor Problem 
 
Check motor armature and wiring for short 
circuits 
Monitor Rev 
 
The revision level of the 
monitor data structure shared 
between the line and motor 
side processors does not 
match.   
Software Problem 
 
Re-load proper software into both processors 
MS Size 
 
The motor side power 
converter has detected that 
the power bridge and current 
sensors, do not match. 
Hardware Mismatch 
 
Size of the power bridge does not match the 
rating as defined on the cube ID board.   
 
Check for correct Cube ID board located on A4 
board 
MTR Data Flt 
 
Motor parameters checksum 
is invalid. 
Parameters Corrupted 
 
Check & re-enter Motor Side (A4) parameters 
and power cycle the drive 
 
If re-occurs, replace Drive Control board A2 
Mtr Overload 
(alarm) 
 
The motor had exceeded the 
user defined motor overload 
curve.  
 
Verify Overload Curve Parameters 
 
Check both OVLD START LEVEL (A5) and 
OVLD TIME OUT (A5) parameters. 
Excessive Field Weakening 
 
Verify that FULL FLD AMPS (A5) and WAEK 
FLD AMPS (A5) are set correctly so that motor 
can produce rated torque 
 
Verify that motor armature voltage is correct 
for applied speed and load 
Accurate Motor Parameters 
 
Verify motor nameplate values are entered 
correctly 
Excessive Current Draw 
 
Decrease accel/decel rate 
 
Verify elevator counterweights 
 
Verify mechanical release of elevator brake 
Motor Problem 
 
Check for motor failure 
 
Check for faulty motor wiring 
No Drv 
Handshake 
(operator serial 
link error) 
The operator lost 
communications with the 
drive’s control board. 
 
Bad Connector Connection 
 
Remove and re-seat the operator in its cradle. 
 
If re-occurs, the operator or the drive’s control 
board may need to be replaced. 
90