Viking AF/AR Benutzerhandbuch

Seite von 26
42
41
General Information
Water Supply Requirements
Use only 1/4” (6 mm) copper tubing for
water line. Do Not install copper tubing in
area where temperatures drop below
35˚ F (1.7˚ C). Before attaching copper
tubing to the unit, flush at least 2 quarts
(1.9 L) of water through the copper tubing
and into a bucket to remove any particles
in the water line.
• Viking Range Corporation is not
responsible for property damage due to
improper installation or water
connection.
• Connect 1/4” (6mm) flexible copper tubing
to household plumbing in compliance with
local codes and ordinances.
• Length of copper tubing must reach from
water supply connection to the unit
connection with an additional length to
facilitate moving the unit out of enclosure
for cleaning or service. Tubing should be
soft instead of rigid and ends should be
free of burrs.
• Copper tubing route must be above 35˚ F
(1.7˚ C) to prevent water line from freezing.
• Do not use plastic water lines from the
household plumbing to the water inlet
valve connection on the refrigeration
unit.
• Do not use the self-piercing feature of a
saddle valve. The hole made by the
piercing lance is too small for the water
flow rate required by the ice maker.
• If saddle valve is not used, place a
separate shut-off valve in an easily
accessible location between water supply
and the unit. Do not locate shut-off valve
behind the unit.
• The installation of Viking units with a
reverse osmosis system is acceptable
as long as the water pressure remains
within the allowable PSI as stated below.
It is important to note that with many
reverse osmosis systems, the pressure
starts off high, but then it decreases as the
water level of the reverse osmosis storage
area drops. This must be considered when
checking the water pressure coming into
the unit.
• Connect a vertical or horizontal 1/2” (1.2
cm) to 1 1/4” (3.2 cm) COLD water line
near water area.
• Run water line through the floor, back, or
side wall. Tubing should lay flat on floor
underneath the unit. Clamp tubing to wall
or floor.
• Water pressure must be greater than 20 psi
and less than 120 psi on non-dispensers
and greater than 35 psi and less than 120
psi on dispensers.
General Information
Area Requirements
Verify the following:
• Unit can fit into residence and can be
moved around corners and through
doorways.
• Floors can support unit’s weight plus food
weight (approximately 1200 pounds [540
kg] per unit).
• Rear wall is solid and is able to support
two (2) horizontally mounted 2X4s
(included) bolted to 2 wall studs. The 2X4
board bolt heads must be flush with 2X4
to prevent obstruction.
• Remove anything attached to rear or side
walls that can obstruct unit installation.
• Cutout dimensions are accurate.
• Electrical outlet is in correct location.
• Water line is in correct location.
• Do not install a refrigeration unit near a
heat source, nor in a location where the
surrounding temperature will fall below 60º
F (16º C).
Electrical Requirements
It is the customer’s responsibility to:
• contact a qualified electrical installer.
• assure that the electrical installation is
adequate and in conformance with the
National Electrical Code, ANSI/NFPA 70-
latest edition or Canadian Electrical Code
C22.1-1998 and C22.2 No. 0-M91 (or
latest edition), and all local codes and
ordinances. A 115 volt, 60-Hz, 15 amp,
fused, electrical supply is required. It is
required that a separate circuit serving only
this appliance be provided. This appliance
is equipped with a power supply cord
having a 3-prong grounding plug. To
minimize possible shock hazard, the cord
must be plugged into a mating 3-prong,
grounding-type wall receptacle.
Do not use an extension cord.
If codes permit a separate grounding wire to
be used, it is recommended that a qualified
electrician determine that the grounding
path is adequate.
DO NOT ground to a gas pipe. Check with
a qualified electrician if you are not sure the
appliance is properly grounded. DO NOT
have a fuse in the neutral or grounding
circuit.
Anti-Tip Requirements
The anti-tip boards should be fastened
into position prior to moving the unit into
the opening.
Note: Additional mounting boards may
be required if the unit does not touch
the back wall of the enclosure. To
prevent unit from tipping forward, it
must be secured in place with a solid
soffit or wood block.
W A R N I N G
To avoid serious illness or death, do not use unit
where water is microbiologically unsafe or of
unknown quality without adequate disinfection
before or after the system. Systems certified for cyst
reduction may be used on disinfected water that
may contain filterable cysts. The contaminants or
other substances removed or reduced by this water
treatment system are not necessarily in you water.