Omron 3G3FV-PDRT1-SIN Benutzerhandbuch

Seite von 161
7-22
7-3-3 Writing Parameter Data
This programming example is designed to write the parameter data in the 3G3FV Inverter. After writing
has been completed, be sure to send an enter command to enable the written data as the Inverter op-
eration data.
To use special remote I/O, it will be necessary to switch the remote I/O operation. Refer to 5-3 Switching
Remote I/O Operation
 and change to the special remote I/O operation.
H
Allocations
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Write Parameter Input Bit
Faulty Data Reset Input Bit
Data Write Flag
Sending Enter Command Flag
Setting “00” Function Code Flag
Data Write Completed Flag
Data Agree Flag (Function Code and Register No.)
Sending Written Data Flag
00000
00002
03000
03005
00100
00101
00102
00103
03010
Register number of the parameter to be written
Written data
Faulty Data Flag
DM 0000
DM 0001
D
Remote I/O Allocation Areas
I/O classification
Word
15 to 8
7 to 0
Output
n
Register number (leftmost byte)
Function code (10: Write, 03: Read)
(PC to 3G3FV
n+1
Register data (leftmost byte)
Register number (rightmost byte)
Inverter)
n+2
Not used
Register data (rightmost byte)
Input
m
Register number (leftmost byte)
Function code (10: Write, 03: Read)
(3G3FV Inverter to
m+1
Register data (leftmost byte)
Register number (rightmost byte)
PC)
m+2
Not used
Register data (rightmost byte)
Communications Programs
 (SYSMAC C200HX/HG/HE PCs)
Chapter 7