Omron 3G3FV-PDRT1-SIN Benutzerhandbuch

Seite von 161
1-10
1-3-3 CompoBus/D Communications Specifications
Item
Specifications
Communications protocol
DeviceNet
Supported connections (commu-
nications)
Master-Slave:
Remote I/O and explicit messages
Peer-to-peer: FINS 
messages
Both conform to DeviceNet specifications.
Connection forms
Combination of multi-drop and T-branch connections (for trunk and drop
lines)
Baud rate
500 Kbps, 250 Kbps, or 125 Kbps (switchable)
Communications media
Special 5-wire cables (2 signal lines, 2 power lines, and 1 shield line)
Thick Cable:
DCA2-5C10 (100 m)
Thin Cable: 
DCA1-5C10 (100 m)
Communications
distances
500 Kbps
Network length:
100 m max.
Drop line length: 
6 m max.
Total drop line length: 
39 m max.
250 Kbps
Network length: 
250 m max.
Drop line length: 
6 m max.
Total drop line length: 
78 m max.
125 Kbps
Network length: 
500 m max.
Drop line length: 
6 m max.
Total drop line length: 
156 m max.
Communications power supply
24 VDC 
$
1%, supplied externally
(Slave power supply: 11 to 25 VDC)
Recommended power supply: OMRON S82H Series or S82J Series
Max. number of nodes
64 nodes
Max. number of Masters
Without Configurator:
1
With Configurator:
63
Max. number of Slaves
Without Configurator:
63
With Configurator:
63
Error control
CRC check
1-3-4 Inverter
The maximum number of Inverters that can be connected to one Network depends on the PC model
that is used, the remote I/O functions of the Inverter, and whether message communications are used or
not. (Use the message communications function for setting some parameters and for monitoring the
output current.) The differences between models are provided in the following tables.
Functions and System Configuration
Chapter 1