5-14
D
C: Beginning Control Code Word
Specify the beginning word address of the area for storing the required control codes for message com-
munications. The control codes shown in the following table are required by CompoBus/D Master Units.
Preset the data in consecutive words.
munications. The control codes shown in the following table are required by CompoBus/D Master Units.
Preset the data in consecutive words.
Word address
Bits
15
14 to 8
7 to 0
C
Number of command data bytes: 0000 to 00A0 hex (0 to 160 bytes)
Set the amount of data from the beginning S word.
Set the amount of data from the beginning S word.
C+1
Number of response data bytes: 0001 to 00A0 hex (0 to 160 bytes)
Set the size of the data storage area from the beginning D word.
Set the size of the data storage area from the beginning D word.
C+2
Network address: 0001 to 007F hex (1 to 127)
When using CMND(194) with the CV Series, a network address must be set for each
CompoBus/D Master Unit. The network address is edited using the routing table edit
function of a Peripheral Device (except for the Programming Console).
When using CMND(194) with the CV Series, a network address must be set for each
CompoBus/D Master Unit. The network address is edited using the routing table edit
function of a Peripheral Device (except for the Programming Console).
C+3
Command destination node address: 00 to
3F hex (0 to 63)
Node address of the Master Unit
3F hex (0 to 63)
Node address of the Master Unit
Command destination Unit address
Set Master Unit (FE) or Master Unit’s unit
number, 10 to 1F hex (0 to 15).
Set Master Unit (FE) or Master Unit’s unit
number, 10 to 1F hex (0 to 15).
C+4
Response Communications port no.: 0 to 7
Number of retries: 00 to 0F hex (0 to 15)
Set the number of times to resend for error
response.
Set the number of times to resend for error
response.
C+5
Response monitor time:
0000 hex
→
2 s
0001 to 028F hex
→
0.1 to 65.5 s (unit: 0.1 s)
Set at least 2 seconds for explicit messages.
Note Set “0” in word C+4 bit 15 to require a response or “1” to not require a response. Responses are
required for explicit messages, so set “0.”
H
Message Timing
When executing CMND(194), an AND condition must be set that requires both the PC’s Network Com-
munications Enabled Flag and the Master Unit’s Message Communications Enabled Flag to be ON.
munications Enabled Flag and the Master Unit’s Message Communications Enabled Flag to be ON.
(194)
CMND
CMND
S
D
C
Execution condition
Network Communications
Enabled Flag
Message Communications
Enabled Flag
H
Message Response Read Timing
Have messages read with the rising edge of the Network Communications Enabled Flag for each com-
munications port.
munications port.
Response read
processing
Enabled Flag
Network Communications
CompoBus/D Communications Card Operations
Chapter 5