5.3 Parameterization
M200D AS-Interface Basic
72
Manual, 03/2009, A5E01668085-01
5.3.2
Parameterization via local setting
Setting the current limit value
The rotary coding switch for setting the operating current I
e
(0.15 … 2 A, 1.5 … 9 A or
1.5 … 12 A depending on the device version) is located under the cover on the front of the
starter.
le
0,4
0,3
0,2
0,15
2A1,8
1,5
1,2
1
0,8
0,6
OFF
CLASS
Figure 5-1
Rotary coding switch with 2 A scale
Before commissioning the motor starter, set the operating current I
e
for the overload trip:
Step
Procedure
1
Open the transparent cover at the top of the housing for the motor starter.
2
Use a screwdriver to set the operating current I
e
on the scale of the rotary coding switch.
3
Close the transparent cover.
Note
In the delivery condition, the minimum current limit is set.
Changes to the position of the rotary coding switch require approx. 500 ms to take effect.
In the delivery condition, the minimum current limit is set.
Changes to the position of the rotary coding switch require approx. 500 ms to take effect.