Configuration / parameterization 
 
5.3 Parameterization 
 
M200D AS-Interface Basic 
72
 
Manual, 03/2009, A5E01668085-01 
5.3.2 
Parameterization via local setting 
Setting the current limit value   
The rotary coding switch for setting the operating current I
(0.15 … 2 A, 1.5 … 9 A or 
1.5 … 12 A depending on the device version) is located under the cover on the front of the 
starter. 
le
0,4
0,3
0,2
0,15
2A1,8
1,5
1,2
1
0,8
0,6
OFF
CLASS
 
Figure 5-1 
Rotary coding switch with 2 A scale   
Before commissioning the motor starter, set the operating current I
e
 for the overload trip:   
 
Step 
Procedure 
Open the transparent cover at the top of the housing for the motor starter. 
Use a screwdriver to set the operating current I
e
 on the scale of the rotary coding switch. 
Close the transparent cover. 
 
 
 
Note 
In the delivery condition, the minimum current limit is set. 
Changes to the position of the rotary coding switch require approx. 500 ms to take effect.