water pipinG pressure test
This  section  is  only  for  the  manufacturer  installing  the 
water heater when the installation is to comply with H.U.D. 
Standards.
When  testing  the  water  ways,  H.U.D.  Standards  state: 
“Water  distribution  system:  All  water  piping  in  the  water 
distribution  system  shall  be  subjected  to  a  pressure  test. 
The  test  shall  be  made  by  subjecting  the  system  to  air  or 
water  at  100  psi  for  15  minutes  without  loss  of  pressure. 
when  air  pressure  is  used,  the  water  heater  shall  not 
be  connected  during  the  test.”
temperature- pressure relief valve
This  water  heater  shall  not  be  connected  to  any  heating 
systems or component(s) used with a non-potable water heating 
appliance. 
Toxic chemicals, such as those used for boiler treatment shall 
not be introduced into this system.
Water  supply  systems  may,  because  of  such  events  as 
high line pressure, frequent cut-offs, the effects of water 
hammer  among  others,  have  installed  devices  such 
as  pressure  reducing  valves,  check  valves,  back  flow 
preventers, etc. to control these types of problems.  When 
these devices are not equipped with an internal by-pass, 
and no other measures are taken, the devices cause the 
water system to be closed.  As water is heated, it expands 
(thermal expansion) and closed systems do not allow for 
the expansion of heated water.
The water within the water heater tank expands as it is heated 
and increases the pressure of the water system. If the relieving 
point  of  the  water  heater’s  temperature-pressure  relief  valve 
is  reached,  the  valve  will  relieve  the  excess  pressure. 
the 
temperature-pressure  relief  valve  is  not  intended  for  the 
constant relief of thermal expansion. This is an unacceptable 
condition and must be corrected.
It is recommended that any devices installed which could create 
a  closed  system  have  a  by-pass  and/or  the  system  have  an 
expansion tank or device to relieve the pressure built by thermal 
expansion in the water system.  Expansion tanks are available 
for ordering through a local plumbing contractor.  Contact the 
local water supplier and/or a service agency for assistance in 
controlling these situations.
note:  to  protect  against  untimely  corrosion  of  hot  and 
cold  water  fittings,  it  is  strongly  recommended  that  di-
electric  unions  or  couplings  be  installed  on  this  water 
heater when connected to copper pipe.
figure 4 shows the typical attachment of the water piping 
to the water heater. the water heater is equipped with 1/2 
inch npt water connections.
note:  if using copper tubing, solder tubing to an adapter 
before  attaching  the  adapter  to  the  cold  water  inlet 
connection. do not solder the cold water supply line directly 
to the cold water inlet,  it will harm the dip tube and damage 
the tank.