This  heater  is  provided  with  a  properly  certified  combination  
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory 
that  maintains  periodic  inspection  of  production  of  listed 
equipment of materials as meeting the requirements for Relief 
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, 
and the code requirements of ASME.
If replaced, the valve must meet the requirements of local codes, 
but not less than a combination temperature and pressure relief 
valve certified as indicated in the above paragraph.
The valve must be marked with a maximum set pressure not to 
exceed the marked hydrostatic working pressure of the water heater 
 (150 psi = 1,035 kPa) and a discharge capacity not less than the 
water heater input rate as shown on the model rating plate.
for safe operation of the water heater, the relief valve must 
not be removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly 
into the fitting of the water heater designed for the relief valve.  
Provide tubing so that any discharge will exit only within 6 inches 
(153 mm) above an adequate drain,  or external to the building 
or structure.  Be certain that no contact is made with any live 
electrical part.  The discharge opening must not be blocked or 
reduced  in  size  under  any  circumstances.    Excessive  length, 
over 30 feet (9.14 m), or use of more than four elbows can cause 
restriction and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief valve 
and  the  tank.    Do  not  connect  tubing  directly  to  discharge  drain 
unless a 6 inch air gap is provided.  The relief valve must be allowed 
to  discharge  water  in  sufficient  quantities,  should  circumstances 
demand, to prevent bodily injury, hazard to life, or property damage.  
If the discharge pipe is not connected to a drain or other suitable 
means, the water flow may cause property damage.
The Discharge Pipe:
•  Shall not be smaller in size than the outlet pipe size of the valve, 
  or have any reducing couplings or other restrictions.
•  Shall not be plugged or blocked.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both the  
  temperature-pressure relief valve, and the discharge pipe.
•  Shall terminate at an adequate drain or external to the building 
  or structure.
•  Shall not have any shut-off valve between the relief valve and 
  tank nor in the discharge pipe.
The temperature-pressure relief valve must be manually operated 
at least once a year.  Caution should be taken to ensure that (1) no 
one is in front of or around the outlet of the temperature-pressure 
relief valve discharge line, and (2) the water manually discharged 
will not cause any bodily injury or property damage because the 
water may be extremely hot.
If  after  manually  operating  the  valve,  it  fails  to  completely 
reset  and  continues  to  release  water,  immediately  close 
the  cold  water  inlet  to  the  water  heater,  follow  the  draining 
instructions, and replace the temperature-pressure relief valve 
with  a  new  one.
fillinG  the  water  heater
Never  use  this  water  heater  unless  it  is  completely  full  of 
water. To prevent damage to the tank and heating element, 
the  tank  must  be  filled  with  water.  Water  must  flow  from 
the  hot  water  faucet  before  turning  “ON”  electrical  supply 
to  the  water  heater. The  manufacturer  will  not  warrant  any 
elements  damaged  by  failure  to  follow  instructions.
To  fill  the  water  heater  with  water:
1.  Open  the  cold  water  supply  valve  to  the  water  heater.  
 
note: the cold water supply valve must be left open 
when  the  water  heater  is  in  use.
2.   To  ensure  complete  filling  of  the  tank,  allow  air  to  exit 
by  opening  the  nearest  hot  water  faucet.    Allow  water 
to  run  until  a  constant  flow  is  obtained.   This  will  let  air 
out  of  the  water  heater  and  the  piping.
3.  Check all water piping and connections for leaks.  Repair 
as  needed.
4.  Never  alter  or  modify  the  certified  construction  of  the 
water  heater  or  its  components,  or  bypass  any  safety 
features.  Doing  so  voids  all  warranties.