HEARTH ExTENSION
A hearth extension projecting a minimum of 
20" in front of and a minimum of 12" beyond 
each side of fireplace opening is required to 
protect combustible floor construction in front 
of  fireplace.  Fabricate  a  hearth  extension 
using  a  material  which  meets  the  following 
specifications:  a  layer  of  noncombustible, 
inorganic material having a thermal conduc-
tivity of K=0.84 BTU IN/FT, HR. F (or less) at 
1" thick. For example, if the material selected 
has a K factor of 0.25, such as glass fiber, the 
following formula would apply:
 
0.25 x 1.0" = 0.30" thickness required
 
0.84
Thermal conductivity "K" of materials can be 
obtained  from  manufacturer  or  supplier  of 
noncombustible material. If hearth extension 
is to be covered, use noncombustible mate-
rial such as tile, slate, brick, concrete, metal, 
glass, marble, stone, etc. Provide a means 
to prevent hearth extension from shifting and 
seal gap between fireplace frame and hearth 
extension  with  a  noncombustible  material 
(see Figure 6). 
 WARNING: Hearth extension 
is to be installed only as shown 
in Figure 6.
Fireplace inSTallaTion
Continued
Figure 6 - Hearth Extension
Seal Gap
Fireplace Front
Ember Protector
Fireplace Front 
Raised Hearth
Fireplace Front 
Elevated
Ember Protector
Ember Protector
Seal Gap
Hearth 
Extension
MANTELS
A mantel may be installed if desired (see Figure 
7). Woodwork such as wood trims, mantels or 
any other combustible material projecting from 
front face must not be placed within 12" (36" 
Models)  or  18"  (42/50"  Models)  of  fireplace 
opening. Combustible materials above 12" (36" 
Models) or 18" (42/50" Models) and projecting 
more than 1 
1
/
2
" from fireplace must not be 
placed less than 15" (36" Models) or 21" (42/50" 
Models) from the top opening of the fireplace 
(NFPA STD 211, Sec. 7-3.3.3).
Mantels  or  any  other  combustible  material 
also may come up to side edge of black metal 
face of fireplace as long as projections from 
front face fall within limit shown in Figure 7.
12 
1
/
4
" Ref.
6"
Ref.
15" Min. (3
6"
 M
od
el
s)
21" Min. (4
2/
50
Models)
12" Min.
(36" Models)
18" Min. (42/50"
 
Models)
1
1
/
2
" Max.
3" Nom.
33°
Combustible 
Material
Safe 
Zone for 
Projection of 
Combustible 
Materials
Fireplace Opening
Upper 
Section of 
Fireplace
Figure 7 - Mantel Clearances to 
Combustible Material
FIREBOX
SAFE ZONE
Top View of Fireplace
3" Max.
4.5"
Min. to 
Perpendicular 
Side Wall 
7.75" (36" Models)
11.5" (42/50" Models)
33°
Combustible 
Material Must 
Not Overlap 
Front Face
12" - 36" Models
18" - 42/50" Models