Cisco Cisco Packet Data Gateway (PDG) Installationsanleitung
Technical Specifications
▀ Interface Specifications
▄ ASR 5000 Installation Guide
268
Figure 64. SPIO CO Alarms Cable Assembly
Table 95.
CO Alarms Cable Pinout
CO Alarms IF Pin No.
Cable Wire Color
Cable Terminal Block Position No.
Signal
1
Black
1
Major Alarm - Normally closed
2
Orange
2
Major Alarm - Common
3
Red
3
Major Alarm - Normally open
4
Brown
4
Minor Alarm - Normally closed
5
Yellow
5
Minor Alarm - Common
6
Green
6
Minor Alarm - Normally open
7
Blue
7
Critical Alarm - Normally closed
8
Violet
8
Critical Alarm - Common
9
Gray
9
Critical Alarm - Normally open
10
Not wired
Not equipped
Not applicable
Electrical Characteristics
Each of the three dry-contact relay switches is rated to support a maximum switching current of 1A@30VDC. The relay
contacts should not directly connected to high current devices such as sirens and flashing lamps.
contacts should not directly connected to high current devices such as sirens and flashing lamps.