Chapter 3 Installing the 8106 Server
Tools needed for installation
Warning
Use caution when installing or modifying telephone lines.
Warning
Supplemental earth grounding is required at all times.
Tools needed for installation
Refer to
for a list of tools needed for installation.
Evaluating the site
Before installing the 8106 server, make sure the MeetingPlace System Manager has provided the name
of a site contact who can answer relevant questions regarding the site.
of a site contact who can answer relevant questions regarding the site.
Warning
If any of the requirements in this section have not been met prior to installation, do not proceed with
the installation.
the installation.
Environmental requirements
The recommended operating temperature range for MeetingPlace is 50-95 degrees Fahrenheit (10-35
degrees Celsius), with a non-condensing humidity of 5-80 percent.
degrees Celsius), with a non-condensing humidity of 5-80 percent.
It is essential to keep the server equipment properly cooled. To ensure this, the 8106 server has an
internal fan assembly with four fans to cool the server. To ensure all system components are adequately
cooled, the system must meet these requirements:
internal fan assembly with four fans to cool the server. To ensure all system components are adequately
cooled, the system must meet these requirements:
•
at least 1.5 inches (3.8 cm) of clearance exists in the front and back of the 8106 server
•
at least 0.5 inches (1.25 cm) of clearance exists to the right and left of the 8106 server
•
at least 0.5 inches (1.25 cm) of clearance exists on the top and bottom of the 8106 server
•
all module slots must be filled or covered (use filler panels in empty slots)
•
air flow in an open frame rack or in an enclosed cabinet must be from left to right
Power requirements
Power for the 8106 server must come from a totally dedicated circuit breaker within 8 feet (2.43 meters)
of the equipment. Do not plug any other electrical devices into an outlet connected to the circuit breaker
serving the rack equipment. In addition, the site should have additional power outlets for test and
maintenance equipment.
of the equipment. Do not plug any other electrical devices into an outlet connected to the circuit breaker
serving the rack equipment. In addition, the site should have additional power outlets for test and
maintenance equipment.
MeetingPlace power requirements are 100-240V, 6/3A, 50/60 Hz. If the power in your area is susceptible
to fluctuations or interruptions, consider installing surge suppressors or connecting the servers to an
Uninterruptible Power Supply (UPS). MeetingPlace does not maintain telephony connections should the
system lose power.
to fluctuations or interruptions, consider installing surge suppressors or connecting the servers to an
Uninterruptible Power Supply (UPS). MeetingPlace does not maintain telephony connections should the
system lose power.