Cisco Cisco Unified MeetingPlace Audio Server Maintenance Manual

Page of 313
3-2
Cisco MeetingPlace Audio Server 5.2 Customer Engineering Guide (for Cisco MeetingPlace 8106)
78-16411-01
Chapter 3      Installing the 8106 Server
  Tools needed for installation
Warning
Use caution when installing or modifying telephone lines.
Warning
Supplemental earth grounding is required at all times.
Tools needed for installation
Refer to 
 for a list of tools needed for installation.
Evaluating the site
Before installing the 8106 server, make sure the MeetingPlace System Manager has provided the name 
of a site contact who can answer relevant questions regarding the site.
Warning
If any of the requirements in this section have not been met prior to installation, do not proceed with 
the installation.
Environmental requirements
The recommended operating temperature range for MeetingPlace is 50-95 degrees Fahrenheit (10-35 
degrees Celsius), with a non-condensing humidity of 5-80 percent.
It is essential to keep the server equipment properly cooled. To ensure this, the 8106 server has an 
internal fan assembly with four fans to cool the server. To ensure all system components are adequately 
cooled, the system must meet these requirements:
at least 1.5 inches (3.8 cm) of clearance exists in the front and back of the 8106 server
at least 0.5 inches (1.25 cm) of clearance exists to the right and left of the 8106 server
at least 0.5 inches (1.25 cm) of clearance exists on the top and bottom of the 8106 server
all module slots must be filled or covered (use filler panels in empty slots)
air flow in an open frame rack or in an enclosed cabinet must be from left to right
Power requirements
Power for the 8106 server must come from a totally dedicated circuit breaker within 8 feet (2.43 meters) 
of the equipment. Do not plug any other electrical devices into an outlet connected to the circuit breaker 
serving the rack equipment. In addition, the site should have additional power outlets for test and 
maintenance equipment.
MeetingPlace power requirements are 100-240V, 6/3A, 50/60 Hz. If the power in your area is susceptible 
to fluctuations or interruptions, consider installing surge suppressors or connecting the servers to an 
Uninterruptible Power Supply (UPS). MeetingPlace does not maintain telephony connections should the 
system lose power.