  Troubleshooting 
Detecting Faulty Hardware  ▀   
 
ASR 5500 System Administration Guide, StarOS Release 16  ▄  
 
   
177 
The status of the two Power Filter Units (PFUs) can be viewed by entering the show power chassis command in the 
Exec mode. 
Checking the LEDs on the PFU 
Each PFU has four LEDs along the top edge of its front panel. You must unsnap the top front cover from the chassis to 
view these LEDs. Each LED is associated with one of the four -48 VDC power feeds connected to the PFU.  
Each LED on the PFU should illuminate blue for normal operating conditions.  
Figure 9. 
PFU LEDs 
 
The possible states for these LEDs are described in the following table. If the LED is not blue, use the troubleshooting 
information below to diagnose the problem. 
Table 13. 
PFU LED States 
Color
 
Description
 
Troubleshooting
 
Blue
 
Power feed is supplying -48VDC to 
this power plane
 
None needed.
 
None
 
PFU is not receiving power to one 
or more of its power planes.
 
Verify that each circuit breaker is in the ON position.
 
Verify that the RTN and -48VDC lugs are attached properly to the posts on the 
upper rear of the chassis.
 
Verify that the ground lug is attached properly. 
 
Use a voltmeter to verify that the power distribution panel is supplying the correct 
voltage and sufficient current to the terminals at the rear of the PFU.
 
Check the cables from the power source to the rack for continuity.