Trane N512 Benutzerhandbuch

Seite von 83
Chapter 5 Sequence of operations
38
CNT-SVX07C-EN
Zone temperature control
The Tracer ZN521 zone controller uses two methods of zone temperature 
control:
Cascade zone control—used in the occupied, occupied bypass, and 
occupied standby modes
Simplified zone control—used in the unoccupied mode
Cascade zone control
Cascade zone control maintains zone temperature by controlling the dis-
charge air temperature to control the zone temperature. The controller 
uses the difference between the measured zone temperature and the 
active zone temperature setpoint to produce a discharge air temperature 
setpoint. The controller compares the discharge air temperature setpoint 
with the discharge air temperature and calculates a unit heating/cooling 
capacity accordingly (see Figure 18). The end devices (outdoor air damper, 
valves, etc.) operate in sequence based on the unit heating/cooling capac-
ity (0–100%). 
Figure 18. Cascade zone control 
If the discharge air temperature falls below the Discharge Air Control 
Point Low Limit (configurable using the Rover service tool) and cooling 
capacity is at a minimum, available heating capacity will be used to raise 
the discharge air temperature to the low limit (see “Discharge air temper-
ing” on page 39
).
Simplified zone control
In the unoccupied mode, the controller maintains the zone temperature 
by calculating the required heating or cooling capacity (0–100%) accord-
ing to the measured zone temperature and the active zone temperature 
setpoint. The active zone temperature setpoint is determined by the cur-
rent operating modes, which include occupancy and heat/cool modes.
Active zone 
temperature 
setpoint
Difference
Calculated 
discharge air 
temperature 
setpoint
Calculated unit 
heating/cooling 
capacity
Measured 
zone 
temperature
Measured 
discharge air 
temperature
Difference