Schneider Electric TSXETG100 Benutzerhandbuch

Seite von 2
2
5. Set the COM properties as follows: Bits per second = 19200, Data bits = 8, Parity = None, Stop bits = 1, 
and Flow control = None.
6. Click OK.
7. Start the ETG Setup Utility:
a. Cycle power or press the reset button on the ETG.
b. While the green Power/Status LED blinks rapidly, press Enter on the computer keyboard to access 
the setup utility. See Table 2 for a description of the setup options.
NOTE: The Power/Status LED stops blinking after 5 seconds.
Serial Configuration
1. Start Internet Explorer.
2. In the Address text box, type the IP address assigned to your ETG, then press Enter.
3. Type Administrator for your user name, type Gateway for your password, then click OK.
4. Click Serial Port or Device List as appropriate and proceed to the sections below.
Serial Port
1. Click Serial Port.
2. Select the mode, physical interface, transmission mode, baud rate, and parity for the serial COM port. 
NOTE: Attached serial devices must have the same baud rate, parity, and wiring mode settings. If you are 
using RS485, set the mode according to whether your daisy chain is 2-wire or 4-wire. 
3. If Mode is set to Slave, enter a unique IP address for each remotely connected device. See the User’s 
Guide 63230-319-211 for more information about the slave mode.
4.
Click Apply to save changes.
Device List
For daisy-chain devices on the COM port:
In Master mode, Modbus devices do not have to be defined in the Device List, but it helps you manage 
your system.
To set up the Device List for the ETG:
1. Click Device List.
2. Select the number of viewable devices (1 to 128). The default number of devices is eight. 
3. In Master mode, enter the Local ID for each attached device on the daisy chain. In Slave mode, enter 
the Local IDRemote ID, and select the Connection for each device that needs to be remotely 
connected.
4.
Click Apply.
RS485 Wiring
NOTE: For surge protection, we recommend connecting the shield wire directly to an external earth ground 
at a single point. For instructions on wiring common Schneider Electric devices, see the wiring instructions 
on the ETG100 Technical Library CD.
4-wire Devices
NOTE: The color code shown is for Belden 8723. The color code for Belden 9842 is Blue/White (Tx+), 
White/Blue (Tx-), Orange/White (Rx+), and White/Orange (Rx-).
2-wire Devices
Daisy Chain Maximum Distances
RS485 Biasing and Termination
RS232 Serial Port
NOTE: The ETG pinout for the RJ45 (RS232) is compliant with the EIA/TIA-561 standard. To ensure 
proper connections with other Schneider Electric products, examine the wiring for each device. See the 
wiring instructions on the ETG100 Technical Library CD for more information, or contact your local 
Schneider Electric support representative.
The RS232 port is used to configure the ETG network parameters, and also can be used for serial 
communication using Modbus. The ETG RS232 port is wired as a data terminal equipment (DTE) device 
and uses a standard RJ45 connector. 
NOTE: An RJ45 to DB9 adapter is included in the TCSEAK0100 configuration kit (sold separately) for use 
with an Ethernet crossover cable.
Table 2:
ETG Setup Utility Options
Option
Description
Setting
1
Used to select the language for the current 
HyperTerminal session.
English, French, Spanish, German
Default: English
2
Used to select the format for data sent over an 
Ethernet connection.
Ethernet II, 802.3 SNAP
Default: Ethernet II
3
Used to enter the static IP address of the ETG.
NOTE: If you enter an IP address that is already 
in use, you will be prompted to select a different 
IP address.
0.0.0.0 to 255.255.255.255
Default: 169.254.0.10
4
Used to enter the subnet mask of your network.
0.0.0.0 to 255.255.255.255
Default: 255.255.0.0
5
Used to enter the default gateway (router) IP 
address used for wide area network (WAN) 
communications.
0.0.0.0 to 255.255.255.255
Default: 0.0.0.0
6
Used to define the physical Ethernet 
connection.
10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTx-HD
100BaseTx-FD
Default: 10T/100Tx Auto
7
Saves the settings and exits the setup utility.
Parameter
Options
Default Setting
Mode
Master, Slave
Master
Physical Interface
RS485 4-wire, RS485 2-wire, RS232
RS485 2-wire
Transmission Mode
Modbus RTU, Modbus ASCII
Modbus RTU
Baud Rate
2400, 4800, 9600, 19200, 38400, 56000
, 57600
19200
Parity
Even, Odd, None
Even
 RS232/Modbus ASCII only.
(1) Tx+ (TXD1)
(2) Tx- (TXD0)
(3) Rx+ (RXD1)
(4) Rx- (RXD0)
(5)
Rx+
Rx-
Tx+
Tx-
Rx+
Rx-
Tx+
Tx-
Rx+
Rx-
Tx+
Tx-
Up to 32 devices.
ETG
Belden 8723 or 9842
Slave 1
Slave 2
Green
White
Red
Black
Slave 3
Two (2) 
Terminators 
(120
Ω
 resistor)
Shield
Terminators
(3) Rx+ (D1)
(4) Rx-  (D0)
(5)
L+
L-
L+
L-
L+
L-
Up to 32 devices
ETG
Belden 9841
Slave 1
Blue
White
Slave 3
Terminator 
(120
Ω
 resistor)
Shield
Slave 2
Terminator
Baud Rate
Max. distance for 1–16 devices
Max distance for 17–32 devices
2400
10,000 ft (3,048 m)
5,000 ft (1,524 m)
4800
10,000 ft (3,048 m)
5,000 ft (1,524 m)
9600
10,000 ft (3,048 m)
4,000 ft (1,219 m)
19200
5,000 ft (1,524 m)
2,500 ft (762 m)
38400
5,000 ft (1,524 m)
1,500 ft (457 m)
NOTE: This table is only to be used as a guide.
1
Tx
2
Rx
3
Rx-
4
Rx+
5
6
+
Dip switch settings 
shown are the 
recommended settings 
for 4-wire and 2-wire 
daisy chains. The 2-
wire dip switch settings 
are the default.
Dip Switch Settings
4-wire
2-wire
UP/ON DOWN/OFF
Jum
per
 (
2
-w
ir
e)
Bia
s
Te
rm
ina
tion
ON
OFF
SPECIFICATIONS
MAINTENANCE AND TROUBLESHOOTING
Maintenance
The ETG does not require maintenance, nor does it contain any user-serviceable parts. If the ETG 
requires service, contact your local sales representative for help. Refer to the technical support contacts 
provided in the shipping carton for a list of support phone numbers by country. Do not open the ETG 
enclosure; this will void the product warranty agreement.
Diagnostics
The Diagnostics page served by the ETG, displays diagnostic data that may be helpful in troubleshooting 
network problems. This page also contains information about your specific ETG, including the serial 
number, manufacturing date, and media access control (MAC) address. Clicking the Reset button on this 
page clears all cumulative counters.
NOTE: This page will show accumulated readings since the ETG was last activated. If power to the ETG is 
lost, all values reset to zero.
Troubleshooting
Table 3:
RS232 Pin Assignments (EIA/TIA-561 for RJ45)
Pin No.
Description
Pin 1
Data Set Ready
Pin 2
Received Line Signal Detector (Data Carrier Detect)
Pin 3
Data Terminal Ready
Pin 4
Signal Ground
Pin 5
Received Data
Pin 6
Transmit Data
Pin 7
Clear To Send
Pin 8
Request To Send
Control Power Input
Power-over-Ethernet
Class 3
Operating Input Range
24 Vdc (±10%) sourced by Class 2 rated power 
supply
Burden, maximum
4 W
Isolation
1.5 kV
Environmental
 Ambient Operating Temperature
0°C to
 + 60°C
 Storage Temperature
–40°C to +85°C
 Humidity Rating
5–95% Relative Humidity (non-condensing) at 
+55°C
 Pollution Degree
Class 2
Physical
 Weight
6 oz. / 170 g
 Dimensions
Height (3.18 in. / 80.8 mm), 
Width (2.83 in. / 72 mm), 
Depth (2.59 in. / 65.8 mm)
Enclosure
IP30
Regulatory/Standards Compliance for Electromagnetic Interference
Emissions (radiated and conducted)
EN 55022 / EN 55011 / FCC Class A
Immunity for Industrial Environments:
Electrostatic Discharge
Radiated RF
Electrical Fast Transients
Surge
Conducted RF
Power Frequency Magnetic Field
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6 
EN 61000-4-8 
Regulatory / Standards Compliance for Safety
International (CB Scheme)
IEC 60950
USA
UL 508 / UL 60950/ISA 12.12.01
Canada
cUL (complies with CSA C22.2, #60950)
Europe
EN 60950
Australia / New Zealand
AS/NZS 60950
Other Regulatory / Standards Compliance
Europe
CE
Transparent Ready
B15
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This equipment must be installed and serviced only by qualified personnel.
Qualified persons performing diagnostics or troubleshooting that require electrical conductors to be 
energized must comply with and follow safe electrical work practices. For example, in the USA, see 
NFPA 70E.
Failure to follow these instructions can result in death or serious injury.
Problem
Possible Cause
Solution
Power/Status LED 
is not lit.
Source power is not 
applied or is not stable.
Apply power or check power source.
LED is burned out.
Check to see if other LEDs operate properly.
Ethernet link LED 
is not lit.
Proper link is not 
established.
Make sure the proper cable is used and connected.
Make sure the proper media type is selected in the ETG 
Communications setup configuration.
Power/Status LED 
repeats a four 
blink-pause 
pattern
The IP address that the 
ETG was assigned is 
being used by another 
networked device.
Assign a new IP address to the ETG or to the conflicting 
device.
NOTE: When a duplicate IP address is detected, the ETG 
resets its specified IP address to the default IP address. 
When the ETG detects the conflict no longer exists, it will 
use the specified IP address.
Cannot browse the 
ETG.
Incorrect network 
configuration.
Verify all IP parameters are correct.
Verify ETG receives requests (ping ETG by going to DOS 
prompt and typing “ping” and the ETG IP address, e.g., 
ping 169.254.0.10).
Verify all browser internet options connections settings 
are correct.
Forgot 
administrator 
password.
Call your local sales representative for assistance.
Problem
Possible Cause
Solution
This product must be installed, connected, and used in compliance with prevailing 
standards and/or installation regulations. As standards, specifications, and designs change 
from time to time, please ask for confirmation of the information given in this publication.
www.schneider-electric.com
© 2009 Schneider Electric. All Rights Reserved.