B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
7-2-2. Neither fan motor nor compressor motor runs.
A. Power is not supplied.
B. Check "MODE selector" on the control panel.
C. Check transformer.
(Only for heat pump model)
• Check continuity of primary and 
secondary winding to see if the lead 
wires are disconnected.
• Check that MODE selector switch is 
not set at "OFF".
Check PCB Ass'y.
If it is set at OFF.
Set to "COOL" 
or "HEAT". 
Set to "COOL".
(Cooling only models) and
(Cooling & electric heating models)
(Heat pump model)
NO
• Check power supply. 
Power is being supplied to the unit.
Circuit breaker 
is tripped.
Power failure
Reset breaker.
Wait for recovery 
or contact power 
company.
Replace with suitable
one (larger capacity).
NO
Check capacity of circuit breaker.
Capacity of circuit breaker is 
suitable.
Measure resistance of fan motor 
winding.
Measure resistance of compressor 
motor winding.
• Measure resistance of 4-way valve's  
winding.
(Only for heat pump model)
30