MATE SCREENS 
STACKING MENU 
The STACK (stacking) section is used to program the stacking of the FX’s.  An explanation of stacking can be found in the STACKING 
INFORMATION and STACKING INSTRUCTIONS sections of this manual.  The FX’s can be connected in series, parallel or 3-phase for 
higher voltage and/or higher power.  There are four types of stacking available; ‘Classic Stacking’, ‘OutBack Parallel Stacking’, 
‘OutBack Series Stacking’ and ‘3-Phase Stacking’.  The programming of the “master” and “slave” units must be completed with the 
inverters OFF in order to prevent possible problems. 
   
 
ADV/FX/PAGE1--------
choose category:
ADV
INV
CHGR
PG2
ADV/FX/PAGE2--------
choose category:
PG1
GRID
GEN
PG3
ADV/FX/PAGE3--------
choose category:
PG2
AUX
STACK
PG4
ADV/FX/STACK-----P00
Stack 1-2ph Master
phase
DOWN
INC
DEC
PORT
ADV/FX/STACK-----P00
power save level
0
master adjust only
DOWN
INC
DEC
PORT
ADV/FX/STACK-----P00
power save level
1
slave adjust only
DOWN
INC
DEC
PORT
ADV/FX/STACK--------
stacking setup
completed
TOP
ADV
MAIN
 
 
Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is 
displayed.  Selecting <PG2> shows a second screen of categories.   
 
 
Selecting <PG3> shows a third screen of categories.   
 
 
Selecting <STACK> allows adjustment of the stacking set points and operation.   
 
The STACK PHASE screen sets the hierarchy of the FX’s.  If the system is to be stacked, a HUB 
must be included and the FX that is to be the MASTER must be plugged into port 1 of the HUB.  The 
default for every FX is ‘1-2ph Master’.  Pressing PORT will select the next port that a FX is plugged 
into.  When the port for the FX has been chosen, press INC until the proper master or slave type 
appears (1-2ph Master, Classic Slave, OB Slave L1, OB Slave L2, 3ph Master, or 3ph Slave). 
The POWER SAVE LEVEL MASTER ADJUST ONLY is used to set the number of ‘slaves’ that will 
remain ‘On’ when the system is operating at light load levels.   The value corresponds to the rank of 
the SLAVE.  For example, setting this value to 2 allows all SLAVE’s with POWER SAVE LEVEL 
SLAVE ADJUST ONLY (see next screen) values of 2 or less to stay on at all times.  This setting is for 
“OutBack Stacking” methods only (system with “OB Slave L1” or “OB Slave L2” slaves). 
The POWER SAVE LEVEL SLAVE ADJUST ONLY is used to set a slave inverter’s priority for 
operation when the total FX system is operating at medium to heavy loads.  By setting each of the 
slaves to a different number you can control the sequence that the slave inverters are turned on by 
the master inverter.  This setting is necessary for “OutBack Stacking” methods. 
Selecting TOP returns the user to the top of the ADV/FX/STACK menu section.  Selecting ADV 
returns you to the advanced screen to allow selection of another product connected to the MATE.  
Selecting MAIN returns the display to the MAIN screen.