Outback Power Systems vfx 3232m Benutzerhandbuch

Seite von 65
Copyright 2003  
  OutBack Power Systems, Inc.                      
      FX & VFX Series Inverter/Charger System                     Installation & Programming Manual 
19009 62
nd
 Ave NE, Arlington   WA 98223 USA                                                                  
900-0027-1
                                                     
Tel 360 435 6030     Fax 360 435 6019                                                                              
Rev 7.2
      08/26/05                                                     
Page 61
 
MATE SCREENS 
CALIBRATION MENU 
The CAL
 
(calibration) section is used in the factory or field to make fine adjustments in the operation of the FX.  It is particularly useful 
when multiple FX’s are connected together in the different stacking configurations to maximize the performance of the FX’s.   
 
In most cases, the user will not need to adjust these settings from the factory default values.   
 
ADV/FX/PAGE1--------
choose category:
ADV
INV
CHGR
PG2
ADV/FX/PAGE2--------
choose category:
PG1
GRID
GEN
PG3
ADV/FX/PAGE3--------
choose category:
PG2
AUX
STACK
PG4
ADV/FX/PAGE4--------
choose category:
PG3
SELL
CAL
MAIN
ADV/FX/CALIBRATE-P00
vac input
120 vac
adjustment
DOWN
INC
DEC
PORT
ADV/FX/CALIBRATE-P00
vac output
120 vac
adjustment
DOWN
INC
DEC
PORT
ADV/FX/CALIBRATE-P00
battery vdc 12.8 vdc
adjustment
DOWN
INC
DEC
PORT
ADV/FX/CALIBRATION--
calibration setup
completed
TOP
ADV
MAIN
 
 
Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is 
displayed.  Selecting <PG2> shows a second screen of categories.   
 
 
Selecting <PG3> shows a third screen of categories.   
 
 
Selecting <PG4> shows a fourth screen of categories.   
 
 
Selecting <CAL> allows calibration of the AC input, AC output, and battery voltage set points. 
 
The VAC INPUT ADJUSTMENT allows calibration of the AC input voltage.  If the AC source is 
measured and is different than the value read from the MATE, the user can adjust it to match the 
measured value.  This value can be raised by pressing the INC button.  Conversely, this value can 
be lowered by pressing the DEC button.  The value can be raised or lowered up to 2 vac.   
 
The VAC OUTPUT ADJUSTMENT allows calibration of the AC output voltage.  If the AC output is 
measured and is different than the value read from the MATE, the user can adjust the reading to 
match the measured value.  This value can be raised up to 2 vac by pressing the INC button and 
lowered up to 2 vac by pressing the DEC button.  NOTE:  This only affects the MATE's voltage 
display - See page 51 [ADJ. OUTPUT VOLTAGE] for actual adjustment of inverter VAC output. 
The BATTERY VDC ADJUSTMENT allows calibration of the battery voltage.  If the battery voltage 
is measured and is different than the value read from the MATE, the user can adjust it to match the 
measured value.  This value can be raised by pressing the INC button.  Conversely, this value can 
be lowered by pressing the DEC button.  The value can be raised or lowered up to 0.2 vdc for 12V 
battery system, 0.4V for 24V battery systems, and 0.8V for 48Vbattery systems.   
Selecting TOP returns the user to the top of the ADV/FX/CALIBRATION menu section.  Selecting 
ADV returns you to the advanced screen to allow selection of another product connected to the 
MATE.  Selecting MAIN returns the display to the MAIN screen. 
 
 
 
 
END OF ADVANCED MENU SYSTEM