MATE SCREENS 
BATTERY MENU 
The BATTERY menu section allows the user to check the status of the battery voltage and the battery charging process. Both the 
actual battery voltage and the temperature compensated battery voltage are provided. The battery charging process set points are 
displayed along with the associated timer for the charging process. No adjustments are allowed from this section. To change the battery 
charger’s operation, go the ADVANCED programming section.  The values displayed are not defaults.
STATUS/FX/PAGE1-----
choose category:
MODES METER BATT PG2
STATUS/FX/BATT---P00
battery
12.2 vdc
actual
DOWN
STATUS PORT
STATUS/FX/BATT---P00
battery
12.2 vdc
temp compensated
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
absorb
14.4 vdc
set point
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
absorb
01.0 hrs
time remaining
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
float
13.6 vdc
set point
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
float
00.0 hrs
time remaining
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
refloat
12.2 vdc
set point
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
equalize
14.6 vdc
set point
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
equalize
00.0 hrs
time remaining
DOWN
UP
TOP
PORT
STATUS/FX/BATT---P00
battery temp
255
(not in degrees C/F)
DOWN
UP
TOP
PORT
STATUS/FX/BATT------
end of battery menu
UP
TOP
STATUS
MODES   
Shows status and allows adjustment of Inverter, AC input, Charger, Aux, and EQ 
METER      
Provides the AC voltages and currents of the FX 
<BATT> 
   
Provides the battery voltage and charger set points and timers 
PG2   
    
Displays additional sections – ERRORS, WARNINGS and PG3 
Selecting BATT displays the BATTERY ACTUALvoltage measured by the FX. If the RTS battery 
temperature sensor is connected, then the actual battery voltage will probably not equal the 
temperature compensated battery voltage. When charging, the FX uses the temperature 
compensated battery voltage reading (next screen down) to obtain the charging voltages.   
This menu displays the BATTERY TEMP COMPENSATED voltage which is used by the battery 
charger for regulation. The Remote Temperature Sensor (RTS) must be connected to the Master FX 
for temperature compensation.  If the RTS is connected then this value will be higher than the 
ACTUAL BATTERY VOLTAGE when the battery is hot and will be lower than the actual battery 
voltage when the battery is cold.  Refer to this value to verify the state of the charging process. 
This is the battery charger set point for the absorb stage of the battery charging process.  The 
voltage will be held at the ABSORB SET POINT voltage level for the ABSORB TIME LIMIT period 
that is set in the ADVANCED menu section.  This value can only be changed in the ADVANCED 
menu. 
The ABSORB TIME REMAINING is the period of time remaining for the absorb cycle.  When the FX 
is performing an absorb charge this time value will start counting down once the absorb voltage has 
been reached.  When this value reaches 0.0 hrs, the FX will go into SILENT (charger turns off) mode 
until the battery voltage drops to the REFLOAT voltage.  
This is the battery charger set point for the float stage of the battery charging process. After finishing 
the absorb charging stage the charger turns off and waits for the battery voltage to drop to the refloat 
voltage set point before the charger begins to float the battery. The voltage will be held at the FLOAT 
SET POINT 
voltage level for the float time period that is shown in the next screen down. 
The FLOAT TIME REMAINING is the amount of time remaining for the float stage of the battery 
charging process.  The battery charger does not continuously float the batteries.  It instead only floats 
for the FLOAT TIME LIMIT period set in the ADVANCED menu section.  Once the time period has 
been met, the charger turns off (called SILENT on the SUMMARY screen).  Only when the FX is in 
the “Float” charging stage will the “float time remaining” value appear and start to count down.  
The REFLOAT SET POINT is the battery voltage at which the battery charger will restart the float 
charging process and hold it there for the FLOAT TIME PERIOD.  This setting is compared with the 
BATTERY ACTUAL voltage, not the BATTERY TEMP COMPENSATED voltage.  
 
This is the battery charger set point for the equalize stage of the battery charging process. The 
voltage will be held at the EQUALIZE SET POINT voltage level for the equalize time period that is 
programmed in the ADVANCED menu section.  The equalization process must be manually triggered 
while an AC source is connected to the FX’s AC input.  Equalize can be triggered by pressing the AC 
IN button four times, pressing the EQ button then selecting START.  EQ is not temp compensated.  
The EQUALIZE TIME REMAINING is the amount of time remaining for the equalize stage of the 
battery charging process.  Once the EQUALIZE TIME period has been met, the charger turns off.  
When the FX is in the “Equalize” charging stage, the “equalize time remaining” value appears and 
starts to count down. 
 
The BATTERY TEMP is a reference value used by the battery charger when an RTS is connected to 
the FX.  A displayed value of 255 means the sensor is not connected or has been damaged.  At 
normal room temperatures a value around 130 ± 15 will be shown.  As the battery temperature 
increases, the value displayed will get lower and vice versa.   
Selecting TOP returns the user to the top of the STATUS/FX/BATT menu section.  Selecting 