C7400S ENTHALPY SYLK BUS SENSOR
62-0332—03
2
BEFORE INSTALLATION
Review the “Specifications” on page 1 before installing the 
sensor.
When Installing This Product
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check ratings given in instructions and on the product to 
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service 
technician.
INSTALLATION AND SETUP
The following installation procedures should be performed in 
the order listed:
MOUNTING
IMPORTANT
Avoid mounting in areas where acid fumes or other 
deteriorating vapors can attack the metal parts of the 
sensor, or in areas where escaping gas or other 
explosive vapors are present.
IMPORTANT
The sensor must be mounted in a position that 
allows clearance for wiring, servicing, and removal.
The sensor is mounted directly to the sheet metal using self 
tapping sheet metal screws or in the air stream using the duct 
mounting kit. Use #6 or #8 screws (screws are not provided 
and must be obtained separately). Use the dimensions in 
Fig. 1 on page 1 as a guide.
The sensor must be mounted to allow air flow through the 
sensor housing vent slots on the end or side.
The Sylk Bus sensor communicates with a controller (such as 
the JADE™ Economizer Model W7220) on the two-wire 
communication bus and can either be wired using a two pin 
header or using a side connector. The unit pack Sylk Bus 
sensor includes a two pin Euro connector with the packaging. 
The SKU number of the Sylk Bus sensor is C7400S. All OAT 
(Outdoor Air Temperature), RAT (Return Air Temperature) and 
DAT (Discharge Air Temperature) sensors are the same SKU 
number. The sensor is set for the appropriate type of sensing 
using the three position DIP switch located on the sensor. 
OAT position is OFF, OFF, OFF; RAT is ON, OFF, OFF and 
DAT is OFF, ON, OFF. During installation the sensors are set 
for the the appropriate usage. See “Sylk Bus Sensor Wiring” 
on page 3 for DIP switch details.
Once installed, a sensor can be changed to a different 
application by simply changing the DIP switch setting. 
Sensor Mounting
The sensor can be mounted directly on to the sheet metal of 
the unit or can be mounted in the air stream using the duct 
mounting kit. 
The duct mounting kit contains a rod to hold the sensor in the 
duct, a flange to secure the sensor rod to the duct wall and to 
fill the hole, and a gasket to prevent air from leaking through 
the duct wall. See Fig. 2.
The rod has slots for threading the wire to prevent loose or 
hanging wire in the duct and can be adjusted for 6 or 12 inch 
length. The flange has extended relief for ease of mounting. 
See Fig. 3.
Fig. 2. Duct Mounting Kit (Part # 50053060-001).
Fig. 3. Duct Mounting Adjustments.
ROD - 1 PIECE
FLANGE - 1 PIECE
GASKET - 1 PIECE
M32281
WIRE HOLDER
EXTENDED RELIEF
(FOR CORRECT MOUNTING)
M32282
LENGTH ADJUSTS
TO 6 OR 12 INCHES