HEARTH EXTENSION
A hearth extension projecting a minimum of 
20" in front of and a minimum of 12" beyond 
each side of fireplace opening is required to 
protect combustible floor construction in front 
of  fireplace.  Fabricate  a  hearth  extension 
using  a  material  which  meets  the  following 
specifications:  a  layer  of  noncombustible, 
inorganic material having a thermal conductiv-
ity of K=0.84 BTU IN/FT, HR. F (or less) at 1" 
thick. For example, if material selected has 
a  K  factor  of  0.25,  such  as  glass  fiber,  the 
following formula would apply:
 
0.25 x 1.0" = 0.30" thickness required
 
0.84
Thermal conductivity "K" of materials can be 
obtained  from  manufacturer  or  supplier  of 
noncombustible material. If hearth extension 
is to be covered, use noncombustible mate-
rial such as tile, slate, brick, concrete, metal, 
glass, marble, stone, etc. Provide a means 
to prevent hearth extension from shifting and 
seal gap between fireplace frame and hearth 
extension  with  a  noncombustible  material 
(see Figure 3).
 WARNING: Hearth extension 
is to be installed only as shown 
in Figure 3.
FIREPLACE INSTALLATION
Figure 3 - Hearth Extension
Seal Gap
Fireplace Front
Ember Protector
Fireplace Front 
Raised Hearth
Fireplace Front 
Elevated
Ember Protector
Ember Protector
Seal Gap
Hearth 
Extension
Seal Gap
Fireplace Front
Ember Protector
Fireplace Front 
Elevated
Do Not Block Louver
Ember Protector
Seal Gap
Hearth 
Extension
Hearth Extension, Circulating Modes
Hearth Extension, Noncirculating Models
NO