VENTING INSTALLATION
Continued
Figure 9 - Typical Offset Installation
Return 
Elbow
Offset 
Elbow
Return 
Elbow
Offset 
Elbow
6' Max.
6' Max.
6' Max.
6' Max.
6' Max.
6' Max.
Return 
Elbow
Offset 
Elbow
Offset 
Elbow
Return 
Elbow
A
B
C
Offset 
Elbow
Ceiling 
Support Pipe 
12S-8DM
Return 
Elbow
ASSEMBLY AND INSTALLATION OF 
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists 
of a galvanized outer pipe, a stainless steel 
inner flue pipe and a wire spacer. Pipe sec-
tions must be assembled independently as 
chimney is installed. When connecting chim-
ney directly to fireplace, inner flue pipe sec-
tion must be installed first with lanced side 
up. Outer pipe section can then be installed 
over flue pipe section with hemmed end up. 
Press down on each pipe section until lances 
securely  engage  hem  on  fireplace  starter. 
Wire  will  assure  proper  spacing  between 
inner and outer pipe sections.
Note: For Canada, use chimney parts des-
ignated HT.
 Opening in collar around 
chimney at top of fireplace must 
not be obstructed. Never use 
blown insulation to fill chimney 
enclosure.
Continue to assemble chimney sections as 
outlined,  making  sure  that  both  inner  and 
outer pipe sections are locked together. When 
installing double wall snap-lock chimney to-
gether, it is important to assure joint between 
chimney sections is locked. Check by pulling 
chimney upward after locking. Chimney will 
not  come  apart  if  properly  locked.  It  is  not 
necessary to add screws to keep chimney to-
gether (exception - see Figure 11, page 9).
USING ELBOW OFFSETS (30E-8DM)
1.  To achieve desired offset, you may install 
combinations  of  12",  18",  24",  36"  and 
48" length of double wall pipe (see offset 
chart, page 7, and Figure 9).
 
Note: For systems with 2 elbow sets, mini-
mum height is 22 feet. Maximum height 
for any system is 50 feet.
2.  Chimney  weight  above  offset  rests  on 
return  elbow.  Straps  must  be  securely 
nailed to rafters or joists (see Figure 10, 
details A and B, page 9).
3.  Maximum length of pipe between supports 
(return elbow or 12S-8DM) is 6' of angle 
run. Maximum of two 6' angle run sections 
per chimney system (see Figure 9).
4.  All pipe connections between offset and 
return must be secured with two screws 
on outer pipe only (see Figure 11, page 
9). Do not penetrate inner stainless.